Exhaust Airflow Rate Sizing for Single-Glass Greenhouses
Size exhaust airflow for an unshaded clear single-pane glass greenhouse up to 485 ft² (45 m²) at 1.0 to 1.5 ACH/min (60 to 90 ACH/h) at sea level, targeting the upper end when outdoor summer temperatures are warm, crop canopy is sparse, or direct midday sun hits unshaded glass. Clear single-pane glass transmits direct-beam solar radiation with minimal diffusion, creating sharper midday sensible heat spikes than multi-wall polycarbonate or double polyethylene. Apply shading-credit reductions only when exterior or interior shading is actively deployed before peak solar hours, and multiply volumetric airflow by the local altitude density correction factor above 2,000 ft (610 m).
← Target Exhaust Airflow Rates, ACH Conversions & Adjustments
Greenhouse exhaust ventilation & intake area calculator
Compute target summer exhaust airflow, net free intake area by allowable face velocity, and gross louver or insect-screen frame area for Q-P fan matching.
For general multi-glazing sizing rules and baseline temperature-rise targets, see Airflow Rate Sizing.
Boundary Conditions That Change Target Airflow
Three physical conditions shift a single-glass house away from the sea-level unshaded baseline:
- Glazing heat-transfer vs. solar transmission: Single-pane glass has a high conductive U-value of 1.13 BTU/(hr·ft²·°F) (6.4 W/(m²·K)), which loses heat rapidly at night and in winter. At midday under clear sky, however, direct-beam solar transmission overwhelms conductive heat loss whenever outdoor air approaches or exceeds target indoor temperature, forcing mechanical exhaust to remove nearly the full net sensible load.
- Altitude air density: Exhaust fans move a constant air volume, while sensible heat removal depends on air mass. Above 2,000 ft (610 m), thinner air removes less heat per CFM (m³/h), requiring higher volumetric flow to hold the same indoor-to-outdoor temperature rise (delta-T).
- Active shading deployment: Shading reduces exhaust demand only when deployed during peak irradiance. Exterior shade cloth blocks solar energy outside the glass envelope; interior shade cloth intercepts light after it has already entered the house, warming the upper air space and yielding a smaller cooling credit unless exhaust sweeps that upper zone.
Single-Glass Target Specifications
| Operating Condition | Target Exchange Rate | Airflow per 1,000 ft³ (28.3 m³) | When to Use |
|---|---|---|---|
| Unshaded, dense mature canopy | 1.0 ACH/min (60 ACH/h) | 1,000 CFM (1,699 m³/h) | Full-canopy edible crops providing active transpirative cooling |
| Unshaded, sparse canopy or high solar load | 1.25–1.5 ACH/min (75–90 ACH/h) | 1,250–1,500 CFM (2,124–2,549 m³/h) | Young transplants, bare benches, or hot-climate midday peaks |
| Active exterior shading deployed | 0.75–1.0 ACH/min (45–60 ACH/h) | 750–1,000 CFM (1,274–1,699 m³/h) | Exterior shade cloth mounted above glass throughout peak sun |
| Active interior shading deployed | 0.90–1.2 ACH/min (54–72 ACH/h) | 900–1,200 CFM (1,529–2,039 m³/h) | Interior screen deployed; lower credit due to trapped upper heat |
Altitude Density Correction Factors
Divide sea-level required volumetric airflow by the local relative air density (or multiply by the correction factor below) so mass airflow remains constant.
| Site Elevation | Relative Air Density | Airflow Multiplier |
|---|---|---|
| 0 ft (0 m) | 1.00 | 1.00 |
| 2,000 ft (610 m) | 0.93 | 1.07 |
| 4,000 ft (1,220 m) | 0.87 | 1.15 |
| 5,000 ft (1,524 m) | 0.83 | 1.20 |
| 6,000 ft (1,830 m) | 0.80 | 1.25 |
| 8,000 ft (2,440 m) | 0.74 | 1.35 |
Step-by-Step Sizing Procedure
1. Calculate Greenhouse Volume
Measure interior length, width, and mean height (eave height plus half the ridge-to-eave rise for a gable roof):
Volume (ft³) = Length (ft) x Width (ft) x Mean Height (ft)Volume (m³) = Length (m) x Width (m) x Mean Height (m)
Illustrative assumption: A 12 ft x 20 ft (3.66 m x 6.10 m) single-glass gable greenhouse with a 9 ft (2.74 m) mean height has a footprint of 240 ft² (22.3 m²) and an enclosed volume of 2,160 ft³ (61.2 m³).
2. Compute Sea-Level Unshaded Exhaust Airflow
Multiply greenhouse volume by the selected ACH/min (or ACH/h in SI):
CFM_base = Volume (ft³) x Target ACH/minm³/h_base = Volume (m³) x Target ACH/h
(Conversion check: 1 CFM = 1.699 m³/h)
Using the illustrative 2,160 ft³ (61.2 m³) house at 1.25 ACH/min (75 ACH/h):
CFM_base = 2,160 x 1.25 = 2,700 CFMm³/h_base = 61.2 x 75 = 4,590 m³/h
3. Apply Active Shading Credit (Only If Deployed)
Apply a reduction only when shading is physically in place during peak solar hours. Do not credit seasonal shade cloth that is stored off the house or partial coverage that leaves midday sun striking unshaded glass.
- Exterior shading: Reduce target airflow only by the verified net solar-gain reduction (for example, an illustrative 30% airflow reduction for active exterior shading gives
2,700 x 0.70 = 1,890 CFMor4,590 x 0.70 = 3,213 m³/h, equal to0.875 ACH/min). - Interior shading: Apply a smaller reduction than exterior shading of the same nominal shade rating because solar heat already passed through the single-pane glass and warms the air pocket above the screen.
4. Apply Altitude Density Correction
Multiply the sea-level airflow by the elevation multiplier from the table above:
CFM_site = CFM_base x Altitude Multiplierm³/h_site = m³/h_base x Altitude Multiplier
At 5,000 ft (1,524 m), using the 1.20 multiplier on the unshaded illustrative example:
CFM_site = 2,700 x 1.20 = 3,240 CFMm³/h_site = 4,590 x 1.20 = 5,508 m³/h
5. Check Sensible Heat Removal Capacity
Verify that the selected airflow holds midday indoor-to-outdoor temperature rise (delta-T) within crop limits using the shared sensible heat equation:
Q_sensible (BTU/h) = 1.08 x CFM_sea_level x delta-T (°F)Q_sensible (W) = 0.335 x m³/h_sea_level x delta-T (K)
(Use the sea-level equivalent mass flow, or multiply site volumetric flow by the local relative air density before computing Q_sensible.)
At 2,700 CFM (4,590 m³/h) sea-level equivalent and a 10°F (5.6 K) allowable rise:
Q_sensible = 1.08 x 2,700 x 10 = 29,160 BTU/hQ_sensible = 0.335 x 4,590 x 5.56 = 8,550 W
6. Size Intake Area and Verify Fan Static-Pressure Curve
Exhaust fans cannot deliver target airflow against choked intakes:
- Divide target site airflow by allowable intake face velocity to get net intake area.
- Divide net intake area by the louver or insect-screen free-area ratio (from the hardware datasheet) to get gross frame area.
- Sum the static-pressure losses across intake louvers, insect mesh, and exhaust shutters, then select a fan whose published Q-P (airflow vs. static pressure) curve meets
CFM_site (m³/h_site)at that operating static pressure—never from a0 in. w.g. (0 Pa)free-air rating.
Verification Checks
- Midday delta-T check: Measure shaded air temperature at canopy height and outside ambient shade temperature at solar noon on a clear day. If indoor temperature exceeds outdoor ambient by more than
10–15°F (5.6–8.3°C)with the fan running at full speed, airflow is below target or intake restriction is choking the fan. - Intake restriction check: Measure static pressure inside the greenhouse relative to outdoors, or check whether the exhaust shutter opens fully without fluttering and intake air enters smoothly without whistling.
- Electrical circuit budget check: Confirm total continuous load on any shared 120V/15A circuit (exhaust fan running watts plus any continuous circulation fans, pumps, or controllers) does not exceed
1,440 W.
Common Failure Modes
- Selecting fans by free-air (
0 Pa) ratings: Adding an exhaust shutter, intake louver, and fine insect screen introduces static pressure that drops real airflow sharply below the catalog free-air number, causing midday heat spikes. - Claiming exterior-level shade credits for interior cloth: Interior shade cloth heats up inside the glass envelope and convects heat downward unless high-mounted exhaust sweeps the air above the cloth.
- Omitting altitude correction above 2,000 ft (610 m): High-elevation greenhouses hit target volumetric ACH/min while still overheating because lower air density carries less sensible heat per cubic foot (cubic meter).
- Assuming high glass U-value cools the house at noon: Single-glass conduction (
6.4 W/(m²·K)) only sheds heat when outdoor air is substantially cooler than indoor air; on warm sunny days, direct-beam solar transmission dominates and requires full exhaust volume. - Undersized or single-point intakes: A small intake forces high face velocity, raises static pressure, and leaves dead-air hot zones in corners outside the direct intake-to-exhaust airstream.