Lean-To & Attached Greenhouse Heating Loads
Exclude the shared building wall of a lean-to greenhouse from full outdoor exposed-area heat loss when it abuts a conditioned interior, while accounting for reduced temperature difference across unheated buffer walls.
Greenhouse heating load & circuit budget calculator
Size winter greenhouse heat loss from exposed glazing U-values (excluding insulated lean-to walls) plus ACH air infiltration, and verify total branch-circuit load.
This rule changes the steady-state heating calculation in the greenhouse heating loads reference across three distinct boundary conditions:
- Conditioned interior wall (heated living space): Set outdoor conductive loss for the shared wall area to zero when the adjacent interior is maintained at or above the greenhouse setpoint. Only the exposed roof, front wall, and two end walls lose heat to outdoor air.
- Unheated buffer wall (garage, enclosed porch, or shed): Do not zero out the shared wall and do not apply the full indoor-to-outdoor temperature difference. Calculate conductive heat transfer using the shared wall's construction U-value and the reduced temperature difference between the greenhouse setpoint and the buffer space's minimum temperature.
- Partial overlap or knee-wall extensions: Any section of the back wall that extends above the host roofline, past the host building corner, or sits on an uninsulated exposed foundation must be measured as part of the full outdoor exposed envelope.
Although a conditioned shared wall eliminates conductive loss through that plane, the flashing and ledger joint where the lean-to meets the host structure remains an air-leakage path and must be reflected in your air-changes-per-hour (ACH) infiltration rate.
Shared-Wall Boundary Rules & Glazing U-Values
Use the following boundary rules to classify each plane of an attached structure up to 485 ft² (45 m²) before summing total heat loss.
| Shared-Wall Condition | Temperature Difference (delta-T) |
Area & U-Value Treatment | Field Verification Required |
|---|---|---|---|
Conditioned interior (T_adj >= T_in) |
0°F (0 K) for sizing baseline | Exclude shared wall area from Q_env |
Confirm adjacent room stays heated at night during cold snaps |
Unheated buffer space (T_out < T_buffer < T_in) |
T_in - T_buffer |
Include A_shared x U_wall x (T_in - T_buffer) |
Measure or verify minimum T_buffer and wall construction U-value |
| Exposed overhang, parapet, or gable extension | T_in - T_out |
Include full exposed area at its actual glazing or wall U-value | Measure exact dimensions extending beyond the host footprint |
For the exposed glazing planes (roof, front wall, and end walls), apply standard steady-state U-values:
| Exposed Glazing Type | U-Value: BTU/(hr·ft²·°F) | U-Value: W/(m²·K) |
|---|---|---|
| Single polyethylene film | 1.20 | 6.8 |
| Single glass | 1.13 | 6.4 |
| Double polyethylene (inflated) | 0.70 | 4.0 |
| 4 mm twin-wall polycarbonate | 0.69 | 3.9 |
| 6 mm twin-wall polycarbonate | 0.62 | 3.5 |
| 8 mm twin-wall polycarbonate | 0.58 | 3.3 |
| 10 mm twin-wall polycarbonate | 0.53 | 3.0 |
| 16 mm triple-wall polycarbonate | 0.40 | 2.3 |
Governing Steady-State Equations
Compute total steady-state heating demand (Q_total) by summing exposed envelope conduction, any unheated buffer-wall conduction, and air-infiltration sensible heat:
- Exposed envelope conduction (
Q_env):- Imperial (BTU/h):
Q_env = sum(A_i x U_i) x (T_in - T_out) - Metric (W):
Q_env = sum(A_i x U_i) x (T_in - T_out)
- Imperial (BTU/h):
- Unheated buffer-wall conduction (
Q_buffer, if applicable):- Imperial (BTU/h):
Q_buffer = A_shared x U_wall x (T_in - T_buffer) - Metric (W):
Q_buffer = A_shared x U_wall x (T_in - T_buffer)
- Imperial (BTU/h):
- Air-infiltration sensible heat (
Q_inf):- Imperial (BTU/h):
Q_inf = 0.018 x V x ACH x (T_in - T_out) - Metric (W):
Q_inf = 0.335 x V x ACH x (T_in - T_out)
- Imperial (BTU/h):
- Total heating demand (
Q_total):Q_total = Q_env + Q_buffer + Q_inf
Do not add an extra wind-exposure multiplier on top of surface U-values or ACH; wind-driven air exchange is already accounted for in the selected ACH rate.
Step-by-Step Sizing & Worked Example
- Map every surface plane: Measure the front wall, sloped roof, and two trapezoidal end walls separately from the shared back wall. Subtract any opaque insulated knee walls from glazing area and assign them their own wall U-value.
- Classify the shared wall: Exclude the shared wall if it abuts a conditioned space, or assign
T_bufferandU_wallif it abuts an unheated garage or shed. - Calculate internal volume (
V): Multiply length by width by average height ((H_back + H_front) / 2) for a lean-to shed roof. - Select design temperatures and ACH: Subtract your outdoor design night low (
T_out) from your crop setpoint (T_in). AssignACHbased on envelope tightness (typically 0.75–1.5 ACH for hobby polycarbonate structures depending on door and ledger sealing). - Check the electrical circuit budget: If using electric resistance heating on a 120V / 15A continuous circuit, verify that
existing continuous load (W) + heater input (W) <= 1,440 W.
Worked Example (Illustrative Assumptions)
Assume a 12 ft x 8 ft (3.66 m x 2.44 m) lean-to greenhouse (96 ft² / 8.9 m² footprint) attached to a conditioned home maintained at 68°F (20°C).
- Illustrative geometry:
- Back shared wall:
12 ft(3.66 m) wide x10 ft(3.05 m) high =120 ft²(11.15 m²) -> Excluded (Q_shared = 0). - Front wall:
12 ft(3.66 m) wide x6 ft(1.83 m) high =72 ft²(6.69 m²). - Sloped roof:
4 ft(1.22 m) rise over8 ft(2.44 m) run gives a slope length of8.94 ft(2.73 m). Area =12 ft x 8.94 ft = 107.3 ft²(9.97 m²). - Two end walls: average height
(10 + 6) / 2 = 8 ft(2.44 m) x8 ft(2.44 m) width =64 ft²(5.95 m²) each; two walls =128 ft²(11.89 m²). - Total exposed area (
A_exposed):72 + 107.3 + 128 = 307.3 ft²(28.55 m²). - Internal volume (
V):12 ft x 8 ft x 8 ft = 768 ft³(21.75 m³).
- Back shared wall:
- Illustrative climate & glazing parameters:
- Glazing:
8 mm twin-wall polycarbonate(U = 0.58 BTU/(hr·ft²·°F)/3.3 W/(m²·K)). - Design setpoint
T_in = 55°F (12.8°C); outdoor design lowT_out = 20°F (-6.7°C);delta-T = 35°F (19.44 K). - Infiltration rate:
1.0 ACH.
- Glazing:
Calculation:
- Exposed conduction (
Q_env):307.3 ft² x 0.58 BTU/(hr·ft²·°F) x 35°F = 6,238 BTU/h28.55 m² x 3.3 W/(m²·K) x 19.44 K = 1,832 W
- Infiltration sensible heat (
Q_inf):0.018 x 768 ft³ x 1.0 ACH x 35°F = 484 BTU/h0.335 x 21.75 m³ x 1.0 ACH x 19.44 K = 142 W
- Total heating load (
Q_total):6,238 + 484 = 6,722 BTU/h(1,974 W)
Had the 120 ft² (11.15 m²) conditioned shared wall been mistakenly counted as exposed 8 mm polycarbonate, it would have added 2,436 BTU/h (715 W) of phantom load—a 36% overestimate.
Circuit budget check: At 1,974 W, this heating demand exceeds the 1,440 W (4,913 BTU/h) continuous limit of a single 120V / 15A circuit—even before accounting for continuous circulation fans or hydroponic pumps. Upgrading to 16 mm triple-wall polycarbonate (0.40 BTU/(hr·ft²·°F) / 2.3 W/(m²·K)) drops Q_env to 4,302 BTU/h (1,262 W) and Q_total to 4,786 BTU/h (1,404 W), which still leaves only 36 W of headroom for continuous loads on a 1,440 W circuit budget.
Verification Checks
- Verify glazing thickness and wall construction: Confirm polycarbonate wall count and thickness on supplier datasheets rather than assuming nominal sizing, and verify whether any unheated buffer wall contains cavity insulation.
- Check the ledger and flashing seal: Inspect the top ledger board, side wall cleats, and sill plates along the shared wall with a smoke pencil or flashlight test at night; unsealed flashing gaps push actual infiltration well above 1.0 ACH.
- Audit continuous electrical loads: Sum the nameplate wattage of all continuously running circulation fans, exhaust controllers, and hydroponic pumps before subtracting from
1,440 Wto find available heater capacity on a 120V / 15A circuit.
Real Failure Modes
- Treating an unheated garage wall as conditioned: Zeroing out a shared wall that abuts an unheated garage or shed ignores steady-state heat loss into a cold buffer that can drop near freezing during multi-day cold snaps.
- Double-counting wind exposure: Multiplying conductive U-values or ACH by an arbitrary wind factor after already selecting a winter ACH rate inflates heater sizing and causes excessive short-cycling.
- Ignoring partial roof or gable exposure: Omitting the triangular or trapezoidal area where a lean-to roof rises above a lower host wall—or forgetting an uninsulated masonry foundation stem wall—leaves uncalculated conductive losses.
- Tripping breakers during peak cold: Sizing a
1,500 Wplug-in heater onto a 120V / 15A circuit that already carries100–200 Wof continuous pumps and fans exceeds the1,440 Wcontinuous circuit limit and risks tripping protection during unattended winter nights.