Solar Heat Gain and Sensible Cooling Load Sizing
Net greenhouse sensible cooling demand equals transmitted solar radiation after shading minus the fraction absorbed by crop evapotranspiration and envelope losses:
Q_sensible = Q_solar_transmitted * (1 - f_ET) - Q_env_loss + Q_internal
For hobby greenhouses up to 485 ft² (45 m²), sizing cooling solely from floor area or air-exchange rules of thumb fails because glazing Solar Heat Gain Coefficient (SHGC), exterior versus interior shade placement, crop canopy density, and the outdoor-to-indoor temperature difference (T_in - T_out) each swing peak sensible load by 30% to over 100%.
Three boundary conditions control the result:
- Outdoor temperature relative to setpoint (
T_in - T_out): On a cool sunny day (T_in > T_out), conduction and air infiltration remove heat (Q_env_loss > 0), reducing cooling load. On a hot summer day (T_out > T_in), conduction and infiltration add heat (Q_env_loss < 0), increasing net cooling demand. - Shade placement: Exterior shade cloth intercepts solar radiation before it crosses the glazing, dissipating absorbed heat to outdoor air. Interior shade cloth intercepts radiation after it has already entered the envelope, so absorbed heat warms the indoor air and remains part of the cooling load.
- Canopy evapotranspiration fraction (
f_ET): Dense, well-watered edible crops convert a substantial share of transmitted solar energy into latent heat (water vapor) rather than sensible air heating. Empty benches, newly transplanted seedlings, or water-stressed crops pushf_ETtoward zero, converting nearly all transmitted solar energy into sensible heat.
Core Equations and Variable Reference
Keep all underlying calculations aligned to SI units, then convert final outputs to North American units (1 W = 3.412 BTU/h; 1 W/m² = 0.317 BTU/(h·ft²); 1 W/(m²·K) = 0.1761 BTU/(h·ft²·°F)).
1. Transmitted Solar Heat Gain:
Q_solar_transmitted = I_solar * A_eff * SHGC * (1 - f_shade)
2. Envelope Conduction + Infiltration Loss (positive when T_in > T_out; negative when T_out > T_in):
Q_env_loss = [Sum(U_i * A_i) + C_inf * V * ACH] * (T_in - T_out)
3. Net Sensible Cooling Load:
Q_sensible = Q_solar_transmitted * (1 - f_ET) - Q_env_loss + Q_internal
| Symbol | Meaning | North American Unit | SI Unit | Source / How to Verify |
|---|---|---|---|---|
I_solar |
Peak incident solar irradiance on effective aperture | BTU/(h·ft²) |
W/m² |
Local clear-sky solar data for design month and latitude |
A_eff |
Effective solar collection area (footprint or orientation-weighted glazing) | ft² |
m² |
Measured greenhouse floor or sunlit glazing dimensions |
SHGC |
Glazing Solar Heat Gain Coefficient (total solar transmittance + inward absorbed fraction) | dimensionless (0–1) | dimensionless (0–1) | Glazing manufacturer datasheet |
f_shade |
Effective solar attenuation fraction of shading | dimensionless (0–1) | dimensionless (0–1) | Shade cloth datasheet adjusted for exterior vs. interior mounting |
f_ET |
Fraction of transmitted solar energy absorbed by crop evapotranspiration | dimensionless (0–1) | dimensionless (0–1) | Crop canopy coverage and irrigation status |
U_i |
Exposed surface thermal transmittance | BTU/(h·ft²·°F) |
W/(m²·K) |
Glazing U-value table below; exclude insulated lean-to shared walls |
A_i |
Exposed surface area of each glazing or wall section i |
ft² |
m² |
Measured roof and wall areas |
C_inf |
Air-infiltration sensible heat factor | 0.018 BTU/(h·ft³·°F) |
0.335 W/(m³·K) |
Standard dry-air volumetric heat capacity constant |
V |
Enclosed greenhouse air volume | ft³ |
m³ |
Measured footprint area × mean height |
ACH |
Natural air changes per hour (infiltration) | h⁻¹ |
h⁻¹ |
Envelope tightness (typically 0.5–1.5 h⁻¹ for sealed hobby frames; higher for loose overlaps) |
T_in, T_out |
Target indoor dry-bulb temperature and peak outdoor design dry-bulb temperature | °F |
°C |
Crop setpoint and local summer design temperature |
Q_internal |
Continuous internal sensible heat (circulation fans, pumps, non-submerged ballasts) | BTU/h |
W |
Sum of nameplate input W × 3.412 for equipment running at solar peak |
Glazing U-Values and Boundary Parameters
Use the following exposed-surface U-values for conduction heat transfer in Q_env_loss. Exclude insulated lean-to shared walls from exposed area calculations. Verify SHGC on the specific glazing datasheet, because multi-wall sheets with UV or IR coatings have lower SHGC than uncoated sheets of the same thickness.
| Glazing Assembly | U-Value: BTU/(h·ft²·°F) |
U-Value: W/(m²·K) |
Notes for Cooling Sizing |
|---|---|---|---|
| Single-layer polyethylene film | 1.20 |
6.8 |
High conduction gain when T_out > T_in; verify film clarity for SHGC |
| Single-pane glass | 1.13 |
6.4 |
High SHGC (often 0.80–0.86 clear); minimal thermal resistance |
| Double-layer inflated polyethylene | 0.70 |
4.0 |
Lower SHGC than single film due to two-layer reflection |
| 4 mm twin-wall polycarbonate | 0.69 |
3.9 |
Light structural glazing; moderate thermal resistance |
| 6 mm twin-wall polycarbonate | 0.62 |
3.5 |
Common hobby glazing; verify SHGC on sheet datasheet |
| 8 mm twin-wall polycarbonate | 0.58 |
3.3 |
Improved thermal buffer against peak outdoor air |
| 10 mm twin-wall polycarbonate | 0.53 |
3.0 |
Lower conduction gain; slightly reduced light transmission |
| 16 mm triple-wall polycarbonate | 0.40 |
2.3 |
Strongest conductive barrier; lowest solar transmission of polycarbonate options |
Evapotranspiration (f_ET) and Shading (f_shade) Operating Ranges
- Crop Evapotranspiration (
f_ET):- Empty bench / seedling stage (<20% canopy cover):
0.00–0.15. Nearly all transmitted solar energy becomes sensible heat. - Partial canopy (20–60% cover):
0.15–0.30. - Full, well-watered edible canopy (>60% cover):
0.30–0.50.
- Empty bench / seedling stage (<20% canopy cover):
- Shade Placement (
f_shade):- Exterior shade cloth:
f_shadetracks the cloth's rated solar blockage closely because absorbed heat is shed directly to outdoor air. - Interior shade cloth:
f_shadeis substantially lower than the cloth's rated shade percentage because only the outward-reflected portion exits through the glazing; absorbed heat stays inside the greenhouse air volume. See Shading and Cooling for shade cloth optical selection.
- Exterior shade cloth:
Step-by-Step Sizing Procedure (With Worked Example)
Step 1: Measure Envelope Geometry and Set Design Conditions
- Measure floor area
A_floor, enclosed volumeV, and exposed glazing surface areasA_i(roof plus exposed walls). - Set peak outdoor design temperature
T_out, target indoor maximumT_in, and clear-sky peak solar irradianceI_solar.
Illustrative hobby greenhouse (verify all values against your actual structure and datasheets):
- Footprint:
12 ft × 20 ft=240 ft²(3.66 m × 6.10 m=22.3 m²) - Mean height:
8.5 ft(2.59 m), VolumeV = 2,041 ft³(57.8 m³) - Exposed glazing:
650 ft²(60.4 m²) of 8 mm twin-wall polycarbonate (U = 0.58 BTU/(h·ft²·°F)/3.3 W/(m²·K)) - Assumed glazing datasheet
SHGC = 0.72 - Assumed exterior shade cloth
f_shade = 0.40(40% effective solar reduction) - Assumed infiltration
ACH = 1.0 h⁻¹ - Assumed peak horizontal irradiance
I_solar = 269.5 BTU/(h·ft²)(850 W/m²) - Assumed full edible canopy
f_ET = 0.35 - Assumed internal continuous equipment
Q_internal = 0 BTU/h(0 W) for clarity (add fan/pump watts × 3.412 if running at peak sun)
Step 2: Calculate Transmitted Solar Heat Gain (Q_solar_transmitted)
SI: 850 W/m² × 22.3 m² × 0.72 × (1 - 0.40) = 8,189 W
US: 269.5 BTU/(h·ft²) × 240 ft² × 0.72 × (1 - 0.40) = 27,942 BTU/h
Step 3: Apply the Crop Evapotranspiration Reduction (1 - f_ET)
SI: 8,189 W × (1 - 0.35) = 5,323 W
US: 27,942 BTU/h × (1 - 0.35) = 18,162 BTU/h
Step 4: Calculate Envelope Conduction and Infiltration (Q_env_loss)
First compute the combined envelope + infiltration heat transfer coefficient (UA + C_inf * V * ACH):
SI: (3.3 W/(m²·K) × 60.4 m²) + (0.335 W/(m³·K) × 57.8 m³ × 1.0 h⁻¹)
= 199.3 W/K + 19.4 W/K = 218.7 W/K
US: (0.58 BTU/(h·ft²·°F) × 650 ft²) + (0.018 BTU/(h·ft³·°F) × 2,041 ft³ × 1.0 h⁻¹)
= 377.0 BTU/(h·°F) + 36.7 BTU/(h·°F) = 413.7 BTU/(h·°F)
Now evaluate both seasonal boundary cases:
Case A — Hot Summer Peak (
T_out = 95.0°F / 35.0°C,T_in = 82.4°F / 28.0°C):T_in - T_out = -12.6°F (-7.0 K)SI: Q_env_loss = 218.7 W/K × (-7.0 K) = -1,531 W (envelope adds 1,531 W of heat) US: Q_env_loss = 413.7 BTU/(h·°F) × (-12.6°F) = -5,213 BTU/h (adds 5,213 BTU/h) Q_sensible = 5,323 W - (-1,531 W) = 6,854 W (23,375 BTU/h)Case B — Cool Sunny Day (
T_out = 59.0°F / 15.0°C,T_in = 77.0°F / 25.0°C):T_in - T_out = +18.0°F (+10.0 K)SI: Q_env_loss = 218.7 W/K × (+10.0 K) = +2,187 W (envelope removes 2,187 W) US: Q_env_loss = 413.7 BTU/(h·°F) × (+18.0°F) = +7,447 BTU/h (removes 7,447 BTU/h) Q_sensible = 5,323 W - 2,187 W = 3,136 W (10,715 BTU/h)
Step 5: Hand Off Q_sensible to Exhaust Ventilation Sizing
Once Q_sensible is known, convert the sensible heat load into required exhaust airflow using the target indoor-to-outdoor temperature rise (delta_T_vent = T_in - T_out, which must be positive for sensible exhaust cooling to work):
US: CFM = Q_sensible (BTU/h) / [1.08 × (T_in - T_out) (°F)]
SI: m³/h = Q_sensible (W) / [0.335 × (T_in - T_out) (K)]
Note on the hot-summer limit: If T_out >= T_in, exhaust ventilation alone cannot hold T_in below T_out. At T_out = 95°F (35°C), Q_sensible must either be reduced with heavier exterior shading or absorbed via evaporative cooling; otherwise T_in will rise above T_out by delta_T_vent until exhaust airflow balances Q_sensible. For exhaust fan static-pressure selection, intake louver free-area sizing, and evaporative strategies, continue to Shading and Cooling.
Verification Checks
Before locking equipment sizes from this calculation, verify five items against physical measurements and datasheets:
- Glazing
SHGCandU-value match the installed sheet: Confirm exact thickness, wall count, and whether anti-condensate or IR coatings alterSHGCon the manufacturer datasheet. - Exposed surface area excludes shared insulated walls: In a lean-to greenhouse, omit the shared building wall from
Sum(U_i * A_i)unless it is uninsulated glazing. - Empty-house worst case checked: Re-run Step 3 with
f_ET = 0.05if the greenhouse will hold heat-sensitive transplants or operate with mostly bare benches during sunny weather. - Internal loads included: Add continuous circulation fan and hydroponic pump wattage (
W × 3.412 = BTU/h) toQ_sensibleif they run during peak sun. - No wind double-counting: Use a single realistic
ACHvalue inQ_env_loss; do not inflate bothU-values andACHsimultaneously for wind.
Real Failure Modes
- Sizing with a cooling
Q_env_losssubtracted during hot weather: TreatingU × A × |T_in - T_out|as a heat loss whenT_out > T_inunderstates summer cooling load by3,000–10,000+ BTU/h(880–2,930+ W) in a 240–485 ft² (22–45 m²) house, guaranteeing overheating on peak afternoons. - Counting interior shade cloth at its full rated shade percentage: Installing 50% shade cloth inside polycarbonate and setting
f_shade = 0.50ignores the solar energy absorbed by the fabric inside the envelope, leaving indoor air temperatures higher than calculated. - Assuming full-canopy
f_ETyear-round: Usingf_ET = 0.45for a house that is empty or newly planted in late spring underestimates sensible heat by 40% or more just as solar irradiance climbs. - Expecting exhaust fans to cool below
T_out: Handing a largeQ_sensibleto an exhaust fan whenT_outalready equals the crop's maximum safe air temperature cannot prevent crop heat stress; only exterior shading or evaporative cooling lowers sensible load or air temperature below ambient.
Guides in this section (2)
- Solar Heat Gain and Sensible Cooling Load Sizing for Hoop-Tunnel GreenhousesCalculate hoop-tunnel solar heat gain using projected horizontal footprint aperture and polyethylene film solar transmittance rather than curved arch surface area, then convert net sensible gain into BTU/h and W before sizing exhaust.
- Solar Heat Gain and Sensible Cooling Load Sizing for Lean-To GreenhousesExclude the shared opaque building wall from transmitted solar aperture calculations while accounting for single-azimuth glazing exposure and conductive or reflected heat from the attached wall when sizing lean-to cooling loads in BTU/h and W.