Intake Free-Area Sizing for Hoop-Tunnel Greenhouses

Fit the full gross intake area into framed hoop-tunnel end-wall bays at low face velocity—typically 300–450 FPM (1.52–2.29 m/s)—so negative static pressure stays below 0.05–0.10 in. w.g. (12.5–25 Pa) and neither starves the exhaust fan nor pulls flexible polyethylene film inward against the hoops. Unlike rigid-wall structures, curved hoop-tunnel sidewalls lack flat, load-bearing framing for rigid louver cutouts, so 100% of the required gross intake area must be accommodated within the flat framed end wall opposite the exhaust fan.

Cross-section of an arched hoop tunnel greenhouse anchored with ground stakes and lower side roll-up ventilation curtainHOOP TUNNEL & GROUND ANCHORS Arch span He = 0 / sidewall Ground stakes Roll-up venting Curved roof sheds snow; verify film tension & anchors

For the general governing rules across all greenhouse framing types, see intake free-area sizing.


Core Sizing Equations

Hoop-tunnel end-wall openings follow the standard net-to-gross area relationship (A_net = Q / v and A_gross = A_net / R_free), where Q is operating exhaust airflow at design static pressure, v is allowable face velocity, and R_free is the louver or combined screen free-area ratio. See Intake Free-Area Sizing, Face Velocity & Screen Adjustments for the full SI and US equations, combined screen-ratio adjustments, and operating fan-curve calculations. On a hoop tunnel, the entire A_gross must fit within the flat framed end wall opposite the exhaust fan.


Hoop-Tunnel Intake Design Parameters

Because curved polyethylene film cannot support rigid rectangular shutter frames without custom structural box-outs, the end wall must absorb the full A_gross. Keeping face velocity low prevents high pressure drop across the end-wall opening.

Parameter Unscreened Intake Louver Louver + Insect Screen Engineering Basis / What to Verify
Target face velocity (v) 350–450 FPM (1.78–2.29 m/s) 250–350 FPM (1.27–1.78 m/s) Lower v offsets added screen resistance and limits negative tunnel pressure
Typical free-area ratio (R_free) 0.55–0.70 (illustrative) 0.35–0.50 (illustrative) Verify exact free-area ratio or pressure-drop curve on the louver/screen datasheet
Max intake pressure drop <= 0.05–0.08 in. w.g. (12.5–20 Pa) <= 0.08–0.10 in. w.g. (20–25 Pa) Higher negative pressure pulls poly film inward against hoops and reduces fan CFM
End-wall bay placement Symmetrical bays flanking center door Symmetrical bays + exterior/interior screen frame Keeps airflow balanced across both sides of the canopy and clears the curved hoop arch

Note: When an insect screen is mounted over an intake louver, do not size the opening using only the louver's unscreened R_free. Use the manufacturer's combined pressure-drop data or the lower combined effective free-area ratio and lower v.


Worked Example: 12 ft x 24 ft (3.66 m x 7.32 m) Hoop Tunnel

Illustrative assumptions (for a 288 ft^2 / 26.8 m^2 hobby hoop tunnel; verify actual values on your fan and louver datasheets):

  • Target exhaust airflow (Q): 2,400 CFM (4,078 m^3/h, or 1.133 m^3/s) at 0.10 in. w.g. (25 Pa) total static pressure
  • Allowable face velocity (v, unscreened motorized louver): 400 FPM (2.03 m/s)
  • Louver datasheet free-area ratio (R_free): 0.60 (60%)

1. Unscreened Louver Calculation

  1. Net free intake area (A_net):
    • US: 2,400 CFM / 400 FPM = 6.00 ft^2 (864 in^2)
    • SI: 1.133 m^3/s / 2.032 m/s = 0.557 m^2
  2. Gross framed opening area (A_gross):
    • US: 6.00 ft^2 / 0.60 = 10.00 ft^2 (1,440 in^2)
    • SI: 0.557 m^2 / 0.60 = 0.929 m^2
  3. End-wall bay split:
    • A single 38 in x 38 in (965 mm x 965 mm) opening often fouls the center door framing or the curved hoop shoulder on a 12 ft (3.66 m) wide tunnel.
    • Split 10.00 ft^2 (0.929 m^2) symmetrically into two framed bays flanking the entry door: 5.00 ft^2 (720 in^2 / 0.465 m^2) per bay.
    • Cutout dimensions per bay: 24 in wide x 30 in tall (610 mm x 762 mm), giving 720 in^2 (5.00 ft^2 / 0.465 m^2) each and 10.00 ft^2 (0.929 m^2) total.

2. Screened Intake Variant (Same 2,400 CFM / 4,078 m^3/h Tunnel)

If fine insect mesh is added to the same tunnel, reduce target v to 300 FPM (1.52 m/s) and use an illustrative combined R_free of 0.40 (40%):

  1. A_net = 2,400 CFM / 300 FPM = 8.00 ft^2 (0.743 m^2)
  2. A_gross = 8.00 ft^2 / 0.40 = 20.00 ft^2 (1.858 m^2)
  3. Split across two bays: 10.00 ft^2 (1,440 in^2 / 0.929 m^2) per bay (e.g., 30 in x 48 in / 762 mm x 1,219 mm each). If the end-wall bay width between the door stud and curved hoop leg cannot fit 30 in (762 mm), add a framed gable intake above the door or build a stand-off screened intake box on the exterior of the end wall rather than cutting the curved sidewall poly.

Step-by-Step Sizing and Framing Procedure

  1. Determine operating exhaust airflow (Q): Read the exhaust fan's airflow at 0.10 in. w.g. (25 Pa) static pressure from its Q-SP curve. Never size intakes from zero-static free-air fan ratings.
  2. Choose allowable face velocity (v): Select 350–450 FPM (1.78–2.29 m/s) for unscreened louvers, or 250–350 FPM (1.27–1.78 m/s) when insect screening is installed.
  3. Calculate A_net and A_gross: Divide Q by v to get A_net, then divide A_net by the verified datasheet R_free to get A_gross.
  4. Measure flat end-wall bay clearances: On the intake end wall (opposite the exhaust fan), measure the clear horizontal width between the door-frame king stud and the curved hoop-leg framing, and measure vertical height below the curved hoop arch.
  5. Distribute A_gross symmetrically: Divide A_gross across two equal left/right bays flanking the door. If the lower bays cannot fit A_gross, add a third framed louver in the upper gable triangle above the door, or mount an oversized stand-off screen box outside the bay so the screen area exceeds the louver frame area.
  6. Verify total system static pressure: Add the intake pressure drop (from the louver/screen datasheet at your chosen v) to the exhaust fan shutter loss and confirm the total static pressure still delivers your target Q on the fan curve.

Verification Checks

  • Polyethylene film deflection test: Run the exhaust fan at full speed with all doors closed and intake louvers fully open. Flexible sidewall and roof film should stay taut or show minimal inward bow; visible slapping or deep inward cupping against the hoops indicates excessive negative static pressure (undersized A_gross or obstructed screen).
  • Static pressure check: If a handheld manometer is available, measure inside-to-outside differential pressure near the center of the tunnel at full fan speed. Keep total negative pressure within the fan's rated operating point (typically <= 0.10 in. w.g. / 25 Pa).
  • Door and louver swing check: Verify that intake louver blades open freely without hitting exterior framing, snow/ground buildup, or interior crop trellises, and that end-wall entry doors do not slam shut from negative pressure.

Real Failure Modes

  • Cutting rigid louvers into curved sidewalls: Mounting rectangular frames into curved hoop-tunnel poly creates gaps at the corners, concentrates wind and tension stress in the film, and leads to tearing and rainwater leaks. Keep rigid intake frames strictly in the flat framed end wall.
  • Sizing from zero-static fan ratings and ignoring R_free: Using a fan's free-air CFM and treating A_net as A_gross typically undersizes the physical opening by 35–55%, starving the fan, spiking motor amp draw, and pulling poly film inward against hoops.
  • Retrofitting insect mesh onto an existing louver: Clipping fine insect mesh directly onto a louver sized for 400–450 FPM (2.03–2.29 m/s) unscreened flow doubles or triples intake pressure drop unless the screen is mounted on a larger stand-off box or A_gross is upsized.
  • Single off-center intake bay: Placing the entire intake on only one side of the end-wall door creates a high-velocity jet down one aisle while leaving the opposite side of the hoop tunnel hot and stagnant.
  • Placing intakes on the same end wall as the exhaust fan: Short-circuits fresh air straight from the intake back out the fan without sweeping the crop canopy. Always place intakes on the end wall opposite the exhaust fan.