Intake Free-Area Sizing, Face Velocity & Screen Adjustments
Divide target exhaust airflow by an allowable intake face velocity of 250 to 300 ft/min (1.25 to 1.5 m/s) to determine the required net free intake area, then divide that net area by the louver or insect-screen free-area ratio to size the gross wall opening.
Greenhouse exhaust ventilation & intake area calculator
Compute target summer exhaust airflow, net free intake area by allowable face velocity, and gross louver or insect-screen frame area for Q-P fan matching.
Boundary conditions that change the sizing:
- Insect exclusion mesh: Mounting a screen directly across a louver frame multiplies the two restrictions together, often doubling or tripling the required gross opening unless you build an expanded screen plenum behind the louver.
- Mesh fouling: Dust, pollen, and mineral deposits narrow the open area of fine screens over time; target the lower end of the velocity band (250 ft/min [1.27 m/s]) when using insect mesh so normal buildup does not starve the fan.
- Gravity vs. motorized louvers: Gravity-operated shutters may only open partway during low-stage or variable-speed fan operation, reducing their active free-area ratio below the fully open datasheet value.
- Multiple intakes: When splitting intake capacity across two or more openings on the wall opposite the exhaust fan, the sum of their individual net free areas must equal or exceed the calculated net free intake area.
Target exhaust airflow is determined on the exhaust ventilation fan-sizing step using total greenhouse volume and air-change rate for hobby structures up to 485 ft² (45 m²).
Core Sizing Equations
Keep all calculations aligned to consistent units. In North American units, airflow is in cubic feet per minute (CFM) and velocity is in feet per minute (ft/min); in SI units, airflow is in cubic meters per hour (m³/h) and velocity is in meters per second (m/s).
1. Net Free Intake Area (A_net)
- US Customary:
A_net (ft²) = Q_target (CFM) / v_face (ft/min) - SI:
A_net (m²) = Q_target (m³/h) / (v_face (m/s) x 3,600)
2. Gross Opening Area (A_gross)
- Single restriction (louver only, or screen only):
A_gross = A_net / R_free - Louver and screen mounted directly in series on the same frame:
R_combined = R_louver x R_screen, soA_gross = A_net / (R_louver x R_screen)
3. Actual Face Velocity Verification (v_actual)
- US Customary:
v_actual (ft/min) = Q_target (CFM) / (A_gross (ft²) x R_free) - SI:
v_actual (m/s) = Q_target (m³/h) / (A_gross (m²) x R_free x 3,600)
Typical Free-Area Ratios & Sizing Reference
Free-area ratios (R_free) vary by blade spacing, frame thickness, and mesh wire diameter. The values below are illustrative planning ranges; verify the exact free-area ratio on the louver or screen datasheet before cutting framing.
| Intake Component | Illustrative Free-Area Ratio (R_free) |
Net-to-Gross Multiplier (1 / R_free) |
Design Note |
|---|---|---|---|
| Unobstructed vent flap (90° open) | 0.90–1.00 | 1.00–1.11 | Minimal restriction; no pest exclusion |
| Gravity or motorized intake louver | 0.55–0.75 | 1.33–1.82 | Verify ratio at full open blade angle |
| Coarse insect screen | 0.60–0.70 | 1.43–1.67 | Low static-pressure penalty when clean |
| Fine exclusion mesh (aphid/whitefly/thrips) | 0.25–0.55 | 1.82–4.00 | Requires oversized frame or plenum box |
| Louver (0.65) + fine screen (0.50) in series | 0.325 (combined) | 3.08 | Direct frame mount without plenum |
Illustrative Intake Sizing at 250 ft/min (1.27 m/s) Design Face Velocity
| Target Exhaust Airflow | Required Net Free Area (A_net) |
Gross Area: Louver Only (R = 0.65) |
Gross Area: Louver + Screen in Series (R = 0.325) |
|---|---|---|---|
| 1,000 CFM (1,699 m³/h) | 4.00 ft² (0.372 m²) | 6.15 ft² (0.572 m²) | 12.31 ft² (1.14 m²) |
| 2,000 CFM (3,398 m³/h) | 8.00 ft² (0.743 m²) | 12.31 ft² (1.14 m²) | 24.62 ft² (2.29 m²) |
| 3,500 CFM (5,947 m³/h) | 14.00 ft² (1.30 m²) | 21.54 ft² (2.00 m²) | 43.08 ft² (4.00 m²) |
Step-by-Step Sizing Procedure
- Pull operating airflow from the fan curve: Read the target exhaust airflow in CFM (m³/h) at the expected operating static pressure (typically 0.05 to 0.15 in. w.g. [12 to 37 Pa] for small greenhouse exhaust fans), not the zero-head free-air rating.
- Select the design face velocity: Use 250 ft/min (1.27 m/s) as the default target for screened intakes or openings near crop benches. Increase up to 300 ft/min (1.52 m/s) only when wall framing limits opening size and the fan has static-pressure headroom.
- Compute net free intake area: Divide target airflow by the chosen face velocity. For example, 2,000 CFM (3,398 m³/h) at 250 ft/min (1.27 m/s) requires 8.00 ft² (0.743 m²) of net free area.
- Apply component free-area ratios:
- Louver only: Divide
A_netby the datasheetR_louver(for example,8.00 ft² / 0.65 = 12.31 ft²[1.14 m²]). - Louver plus insect screen: Either multiply the ratios (
0.65 x 0.50 = 0.325, giving24.62 ft²[2.29 m²] gross frame area) or keep the louver at 12.31 ft² (1.14 m²) and mount a five-sided box plenum of insect screen behind it whose total screen face area is at least8.00 ft² / 0.50 = 16.00 ft²(1.49 m²).
- Louver only: Divide
- Convert gross area to rough opening dimensions: Convert ft² to in² (m² to mm²) and subtract any interior structural mullions or louver frame flanges. A 12.31 ft² (1.14 m²) net louver opening equals 1,773 in² (1,143,800 mm²), which is satisfied by two 24 in x 38 in (610 mm x 965 mm) intake louvers.
- Check the fan static-pressure curve: Confirm that the combined static pressure drop of the intake louver, insect screen, and exhaust shutter stays below the static pressure point where the fan's Q-P (airflow vs. static pressure) curve drops beneath your target CFM (m³/h).
Verification Checks
- Face velocity check: After selecting standard off-the-shelf louver dimensions, run the verification equation (
Q_target / (A_gross x R_free)) to confirm actual velocity remains at or below 300 ft/min (1.5 m/s). - Blade lift check: Run the exhaust fan at its lowest operating stage and verify that gravity intake blades open to their full angle; partial blade opening increases static pressure and cuts airflow.
- Draft and flow-path check: Stand inside near the crop canopy with the fan at full speed. Air should enter smoothly across the intake without high-velocity cold jets blasting adjacent plants or stalling the exhaust fan motor.
Real Failure Modes
- Fan starvation from unadjusted screen ratios: Adding fine insect mesh directly onto a louver that was sized only for bare-louver flow cuts effective free area roughly in half. Static pressure rises with the square of velocity, pushing the fan up its Q-P curve until actual exhaust airflow collapses.
- Sizing from zero-head fan ratings: Using a fan's 0 in. w.g. (0 Pa) catalog number overestimates real ventilation airflow once louver and screen resistance are present, leading to under-ventilated canopies or mismatched intake sizing.
- Screen fouling between cleanings: Fine thrips and whitefly mesh traps pollen, dust, and foliar spray residue. An intake sized right at 300 ft/min (1.5 m/s) when spotless will cross into fan starvation as soon as the mesh loads with debris.
- Short-circuiting intake placement: Locating the intake high on a sidewall or too close to the exhaust fan lets incoming air bypass the plant canopy, leaving crop-level heat and humidity high even though total CFM (m³/h) meets target.
- Undersized gravity louvers on variable-speed fans: Heavy aluminum gravity blades may only open 25%–35% when a fan throttles down to low speed, starving the fan during mild-weather ventilation stages unless motorized actuators or lighter balanced dampers are used.