Intake Free-Area Sizing for Lean-To Greenhouses
Distribute the required net free intake area across the front kneewall and the exposed opposite gable end bays so three-wall lean-to geometry does not force excessive intake face velocity.
← Intake Free-Area Sizing, Face Velocity & Screen Adjustments
Because an attached lean-to shares one long wall with an existing structure, it loses an entire long sidewall for air entry. Attempting to fit the full intake area onto a single narrow gable end wall—often already reduced by an entry door—forces air through an undersized opening, spiking static pressure drop across louvers and insect screens and starving the exhaust fan on its static-pressure curve.
Boundary conditions that change this layout:
- Exhaust fan placement: Keep all intake openings off the gable end wall that houses the exhaust fan, and leave at least
4–6 ft(1.22–1.83 m) of solid wall between the nearest front-kneewall intake and the fan end wall to prevent airflow short-circuiting. - Insect-screen mesh density: Adding fine insect screening directly over a louver face multiplies the two free-area ratios together, often doubling the required gross frame area compared to an unscreened louver.
- Cold-weather / early-spring operation: Front-kneewall intakes positioned directly below bench height (
18–30 in/457–762 mmabove floor) require motorized or tight-sealing backdraft dampers and upward-angled blades or baffles so cool incoming air mixes above or below root zones rather than blasting edible crops directly. - Parent sizing baseline: Use the general intake free-area sizing reference for base target airflow and static-pressure principles before mapping frames onto lean-to framing bays.
Specifications and Reference Ratios
Use the following design targets and typical component free-area ranges for hobby food-growing lean-to greenhouses up to 45 m² (~485 ft²). Verify exact free-area ratios on the louver and screen manufacturer datasheets before cutting framing.
| Parameter | Target / Typical Range (US) | Metric Equivalent (SI) | Engineering Notes |
|---|---|---|---|
| Target net intake face velocity | 250–350 FPM (max 400 FPM) |
1.27–1.78 m/s (max 2.03 m/s) |
Lower velocity limits static pressure loss and crop draft |
| Motorized / gravity louver free-area ratio | 0.55–0.70 (55%–70%) |
0.55–0.70 |
Varies by blade profile, frame depth, and open angle |
| Standard insect screen free-area ratio | 0.55–0.65 (55%–65%) |
0.55–0.65 |
Mounted in series; reduces combined free area |
| Fine pest-exclusion screen free-area ratio | 0.35–0.50 (35%–50%) |
0.35–0.50 |
Requires oversized plenum or extra wall bays |
| Typical design static pressure (total system) | 0.05–0.125 in. w.g. |
12.5–31.1 Pa |
Must match exhaust fan Q-P curve at target CFM (m³/h) |
Core Sizing Equations
Generic equations for net free intake area from target airflow and face velocity, combined louver-and-screen free-area ratios, gross frame area, and operating fan Q-P curve lookups are covered in Intake Free-Area Sizing, Face Velocity & Screen Adjustments. Once you have the required gross frame area for your target 250–350 FPM (1.27–1.78 m/s) face velocity (never exceeding 400 FPM / 2.03 m/s), use the procedure below to split that area across available lean-to kneewall and opposite gable bays.
Worked Lean-To Distribution Example
Illustrative assumptions:
- Structure:
10 ft × 24 ft(3.05 m × 7.32 m) attached lean-to,240 ft²(22.3 m²) floor area. - Wall constraints: Back
24 ft(7.32 m) wall is attached to the house. West gable end wall (10 ft/3.05 mwide) holds the high exhaust fan. East gable end wall holds a36 in(914 mm) entry door, leaving~7 ft(2.13 m) of usable width. Front kneewall is30 in(762 mm) tall with48 in(1,219 mm) on-center post spacing. - Target exhaust airflow:
2,400 CFM(4,078 m³/h) at0.10 in. w.g.(25 Pa) static pressure. - Allowable net face velocity:
300 FPM(1.52 m/s). - Hardware assumptions (verify on datasheet): Louver free-area ratio
0.65, standard insect screen free-area ratio0.60, givingR_combined = 0.65 × 0.60 = 0.39.
Calculation:
A_net = 2,400 CFM / 300 FPM = 8.00 ft²(0.743 m², or1,152 in²).A_gross = 8.00 ft² / 0.39 = 20.51 ft²(1.906 m²).
Because 20.51 ft² (1.906 m²) cannot fit beside the door on the 10 ft (3.05 m) east gable end wall without crowding the framing, distribute the gross frames across the east gable end and front kneewall bays (keeping the westernmost front bay closed near the exhaust fan):
| Intake Location | Qty | Gross Frame Size (US) | Gross Frame Size (Metric) | Total Gross Area | Combined Ratio | Net Free Area |
|---|---|---|---|---|---|---|
| East gable end wall (opposite fan) | 1 | 36 in × 24 in |
914 mm × 610 mm |
6.00 ft² (0.557 m²) |
0.39 |
2.34 ft² (0.217 m²) |
| Front kneewall bays (east & center) | 4 | 36 in × 18 in |
914 mm × 457 mm |
18.00 ft² (1.672 m²) |
0.39 |
7.02 ft² (0.652 m²) |
| Total distributed intake | 5 | — | — | 24.00 ft² (2.230 m²) |
0.39 |
9.36 ft² (0.870 m²) |
Resulting net face velocity:
v_face = 2,400 CFM / 9.36 ft² = 256 FPM(1.30 m/s), staying safely below the300 FPM(1.52 m/s) limit.
Step-by-Step Sizing and Layout Procedure
- Confirm operating airflow and base gross area: Using the intake free-area sizing reference, establish your exhaust fan's airflow on its Q-P curve at
0.05–0.125 in. w.g.(12.5–31.1 Pa) and compute totalA_netandA_grossat250–350 FPM(1.27–1.78 m/s). - Account for fine pest-exclusion screening: If using fine pest-exclusion mesh (
0.35–0.50open area), build an expanded screened plenum box (2×the louver face area) on the exterior or interior so the screen does not choke the louver. - Measure clear bay dimensions: Measure actual clear opening height and width inside the front kneewall (between bottom plate, glazing sill, and vertical posts) and on the opposite gable end wall (excluding door frames and latch clearances).
- Distribute frames for sweep coverage: Place roughly
25%–35%of the net intake area on the opposite gable end wall and65%–75%along the front kneewall bays farthest from the exhaust fan. Leave the front bay closest to the exhaust fan solid (4–6 ft/1.22–1.83 mminimum separation).
Verification Checks
- Datasheet free-area check: Confirm whether the louver's published free area applies to the exact frame size you are ordering; small frames (
12 in × 12 in/305 mm × 305 mm) have a lower free-area ratio than large frames (36 in × 24 in/914 mm × 610 mm) because the outer perimeter frame occupies a larger share of the opening. - Manometer or smoke-pencil check: With the exhaust fan running at full speed and all doors closed, verify that static pressure drop across the greenhouse envelope stays at or below
0.10–0.125 in. w.g.(25–31 Pa). If the door pulls shut hard or snaps open, intake net free area is still undersized. - Face-velocity spot check: Use a handheld anemometer
2–3 in(50–75 mm) downstream of each open louver; readings should average near your design target without dead stalls or>450 FPM(>2.29 m/s) jets.
Common Failure Modes
- Single-gable-wall crowding: Mounting one large louver on the opposite gable end wall leaves front-bench crops in stagnant air pockets and forces high-velocity air down the narrow back walkway.
- Uncompensated insect screening: Stapling fine mesh over an already-sized louver cuts net free area by
35%–65%, pushing the exhaust fan up its static-pressure curve and dropping actual air exchanges per hour. - Short-circuiting at the fan end: Placing a front-kneewall intake within
4 ft(1.22 m) of the exhaust fan end wall pulls outside air straight to the exhaust blades while the opposite end of the greenhouse overheats. - Zero-head fan sizing: Selecting intakes for a fan's free-air rating rather than its
0.10 in. w.g.(25 Pa) rating leads to mismatched airflow and unnecessary framing cuts.