Envelope Conduction Heat Loss Calculation

Open calculator ↓

Calculate steady-state conductive heat loss across a greenhouse envelope up to 45 m² (~485 ft²) by summing the product of each exposed surface area, its material U-value, and the indoor-to-outdoor temperature difference, returning 0 BTU/h (0 W) whenever outdoor air meets or exceeds the indoor target temperature:

Greenhouse heating load & circuit budget calculator

Size winter greenhouse heat loss from exposed glazing U-values (excluding insulated lean-to walls) plus ACH air infiltration, and verify total branch-circuit load.

Greenhouse geometry & exposed glazing

Lean-to excludes the shared insulated back wall. Hoop uses semi-elliptical/semicircular arch geometry (set eave height = 0 for ground-sprung tunnels). Glazing: 4–10 mm 2W PC = twin-wall, 16 mm 3W PC = triple-wall, double air poly = air-inflated double film; U shown as W/m²K / BTU/(h·ft²·°F). Hobby scope ≤ 45 m² (~485 ft²).

Design temperatures & air infiltration (ACH)

Air infiltration (ACH) captures air leakage and wind exposure directly—do not stack an extra wind multiplier on top.

Known branch-circuit continuous load check

Include all continuous devices sharing the same breaker. Default assumes a known 120V/15A continuous 80% budget (1,440 W) in EN or a conservative dedicated 230V/16A budget assumption (2,800 W) in DE/FR.

  • SI internal equation: Q_cond (W) = Sum(A_i * U_i) * max(0, T_target - T_outdoor)
    • A_i = exposed area of surface i in m²
    • U_i = thermal transmittance of surface i in W/(m²·K)
    • T_target - T_outdoor = temperature difference in K (or °C)
  • North American equivalent: Q_cond (BTU/h) = Sum(A_i * U_i) * max(0, T_target - T_outdoor)
    • A_i in ft², U_i in BTU/(h·ft²·°F), temperatures in °F (1 W = 3.41214 BTU/h)

Boundary Conditions

  • Zero-floor clamp: When T_outdoor >= T_target, delta_T is 0 and conductive heat loss is 0 BTU/h (0 W). Do not allow negative values to act as a cooling credit in heating-load totals.
  • Lean-to shared walls: Exclude insulated walls shared with a conditioned building from the exposed surface sum. Uninsulated walls or walls bordering unconditioned spaces still conduct heat and must be measured.
  • Scope within total heating load: Steady-state conduction accounts only for heat moving through solid glazing and base-panel surfaces. It does not include air-infiltration sensible heat (air changes per hour, ACH) or electrical circuit limits; combine conduction with infiltration and check the 1,440 W continuous 120V/15A circuit budget in Heating Loads.
  • No wind double-counting: Standard glazing U-values already incorporate typical exterior convective film resistance. Do not apply an extra wind-multiplier factor to Q_cond.

Glazing and Envelope U-Value Specifications

Enter the material U-value for each distinct surface group in /greenhouse-climate/#calculator. Where a datasheet reports whole-frame U-values (glazing plus aluminum or wood framing) or insulated opaque knee-wall values, use the verified manufacturer datasheet figure rather than the bare panel value.

Glazing / Envelope Material U-Value: North American (BTU/(h·ft²·°F)) U-Value: SI (W/(m²·K)) Typical Application
Single polyethylene film 1.20 6.8 Seasonal hoop houses
Single glass 1.13 6.4 Traditional glass frames
Double polyethylene film (inflated) 0.70 4.0 Dual-layer film roofs and walls
4 mm twin-wall polycarbonate 0.69 3.9 Light hobby kits
6 mm twin-wall polycarbonate 0.62 3.5 Standard hobby roofs and walls
8 mm twin-wall polycarbonate 0.58 3.3 Four-season hobby greenhouses
10 mm twin-wall polycarbonate 0.53 3.0 Cold-climate sidewalls and roofs
16 mm triple-wall polycarbonate 0.40 2.3 High-insulation roofs and base panels

Step-by-Step Calculation for Mixed Surfaces

  1. Divide the envelope into surface groups: Separate roof planes, sidewalls, end-walls, and base panels whenever they use different materials or thicknesses.
  2. Measure true exposed areas:
    • Roof: Measure along the sloped rafter length (sqrt(run^2 + rise^2)), not the flat floor footprint.
    • Sidewalls: Multiply length by height; split into upper glazing and lower base panel if materials differ.
    • End-walls: Add the rectangular wall area (width * eave_height) and any gable triangles (0.5 * width * ridge_rise).
    • Base panels / knee walls: Multiply exposed perimeter by panel height, omitting any insulated lean-to shared wall.
  3. Assign U-values and compute UA: Convert dimensions to m² (ft² * 0.092903) and multiply each surface area by its SI U-value (W/(m²·K)) to get UA_i in W/K. Sum all UA_i values for the total envelope conductance UA_total.
  4. Apply the clamped temperature difference: Calculate delta_T = max(0, T_target - T_outdoor) in K (°F_diff * 5/9).
  5. Convert to output units: Multiply UA_total * delta_T to obtain Q_cond in W, then multiply by 3.41214 for BTU/h.

Illustrative Mixed-Surface Example

Illustrative assumptions: A freestanding gable greenhouse measuring 12.0 ft x 16.0 ft (3.66 m x 4.88 m, 192 ft² / 17.84 m² footprint), 6.0 ft (1.83 m) eaves, 3.0 ft (0.91 m) gable rise (6.71 ft / 2.04 m sloped rafter length), 2.0 ft (0.61 m) perimeter base panel in 16 mm triple-wall polycarbonate, 4.0 ft (1.22 m) upper sidewalls and end-walls in 8 mm twin-wall polycarbonate, and a 6 mm twin-wall polycarbonate roof. Target indoor temperature is 50°F (10.0°C) against a 20°F (-6.7°C) outdoor low (delta_T = 30°F / 16.67 K).

Surface Group Glazing Material Area (ft² / m²) U-Value (BTU/(h·ft²·°F) / W/(m²·K)) Conductance UA (W/K) Heat Loss (BTU/h / W)
Roof (two slopes) 6 mm twin-wall PC 214.7 (19.94) 0.62 (3.5) 69.80 3,969 (1,163)
Upper sidewalls (2 sides) 8 mm twin-wall PC 128.0 (11.89) 0.58 (3.3) 39.24 2,232 (654)
Upper end-walls (2 ends + gables) 8 mm twin-wall PC 132.0 (12.26) 0.58 (3.3) 40.47 2,301 (674)
Base panel (full perimeter) 16 mm triple-wall PC 112.0 (10.41) 0.40 (2.3) 23.93 1,361 (399)
Total Envelope Mixed 586.7 (54.50) — 173.44 9,864 (2,891)

Note: Individual surface rows sum to 9,863 BTU/h (2,890 W) due to integer rounding; the exact SI total (173.44 W/K * 16.67 K) is 2,891 W (9,864 BTU/h). Because 2,891 W of conductive loss alone already exceeds a 1,440 W continuous 120V/15A circuit budget before adding air-infiltration heat loss, this configuration requires either higher-R glazing, a lower delta_T target, or higher-capacity heating.

Verification Checks

  • Surface-to-footprint ratio: A gable greenhouse's exposed surface area is typically 2.5x to 3.5x its floor footprint (586.7 ft² vs. 192 ft² in the example above). If your summed surface area is close to the floor area, roof pitch and end-wall gables were omitted.
  • Unit consistency: Verify that W/(m²·K) inputs are not mixed with ft² areas. Using 1 W/(m²·K) = 0.1761 BTU/(h·ft²·°F) keeps manual checks aligned with /greenhouse-climate/#calculator.
  • Warm-weather check: Test your formula or calculator entry with T_outdoor set equal to or above T_target; the output must read 0 BTU/h (0 W).

Real Failure Modes

  • Using floor footprint for roof area: Substituting horizontal footprint area for sloped roof area underestimates roof conduction on steep-pitched hobby frames.
  • Applying a single U-value to mixed envelopes: Assigning a wall or triple-wall base-panel U-value to the entire structure hides the disproportionate heat loss through thinner roof glazing.
  • Unsealed multi-wall edges and open vents: Steady-state conduction assumes a closed envelope. Uncapped polycarbonate flutes, warped door sweeps, or cracked vents replace predictable conduction with uncontrolled convective air exchange.
  • Double-counting wind or infiltration: Adding arbitrary wind percentages to Q_cond and then adding full ACH infiltration in Heating Loads inflates heater sizing beyond actual steady-state demand.

Guides in this section (3)