Envelope Conduction Heat Loss Calculation
Calculate steady-state conductive heat loss across a greenhouse envelope up to 45 m² (~485 ft²) by summing the product of each exposed surface area, its material U-value, and the indoor-to-outdoor temperature difference, returning 0 BTU/h (0 W) whenever outdoor air meets or exceeds the indoor target temperature:
Greenhouse heating load & circuit budget calculator
Size winter greenhouse heat loss from exposed glazing U-values (excluding insulated lean-to walls) plus ACH air infiltration, and verify total branch-circuit load.
- SI internal equation:
Q_cond (W) = Sum(A_i * U_i) * max(0, T_target - T_outdoor)A_i= exposed area of surfaceiinm²U_i= thermal transmittance of surfaceiinW/(m²·K)T_target - T_outdoor= temperature difference inK(or°C)
- North American equivalent:
Q_cond (BTU/h) = Sum(A_i * U_i) * max(0, T_target - T_outdoor)A_iinft²,U_iinBTU/(h·ft²·°F), temperatures in°F(1 W = 3.41214 BTU/h)
Boundary Conditions
- Zero-floor clamp: When
T_outdoor >= T_target,delta_Tis0and conductive heat loss is0 BTU/h (0 W). Do not allow negative values to act as a cooling credit in heating-load totals. - Lean-to shared walls: Exclude insulated walls shared with a conditioned building from the exposed surface sum. Uninsulated walls or walls bordering unconditioned spaces still conduct heat and must be measured.
- Scope within total heating load: Steady-state conduction accounts only for heat moving through solid glazing and base-panel surfaces. It does not include air-infiltration sensible heat (air changes per hour, ACH) or electrical circuit limits; combine conduction with infiltration and check the
1,440 Wcontinuous120V/15Acircuit budget in Heating Loads. - No wind double-counting: Standard glazing U-values already incorporate typical exterior convective film resistance. Do not apply an extra wind-multiplier factor to
Q_cond.
Glazing and Envelope U-Value Specifications
Enter the material U-value for each distinct surface group in /greenhouse-climate/#calculator. Where a datasheet reports whole-frame U-values (glazing plus aluminum or wood framing) or insulated opaque knee-wall values, use the verified manufacturer datasheet figure rather than the bare panel value.
| Glazing / Envelope Material | U-Value: North American (BTU/(h·ft²·°F)) |
U-Value: SI (W/(m²·K)) |
Typical Application |
|---|---|---|---|
| Single polyethylene film | 1.20 |
6.8 |
Seasonal hoop houses |
| Single glass | 1.13 |
6.4 |
Traditional glass frames |
| Double polyethylene film (inflated) | 0.70 |
4.0 |
Dual-layer film roofs and walls |
| 4 mm twin-wall polycarbonate | 0.69 |
3.9 |
Light hobby kits |
| 6 mm twin-wall polycarbonate | 0.62 |
3.5 |
Standard hobby roofs and walls |
| 8 mm twin-wall polycarbonate | 0.58 |
3.3 |
Four-season hobby greenhouses |
| 10 mm twin-wall polycarbonate | 0.53 |
3.0 |
Cold-climate sidewalls and roofs |
| 16 mm triple-wall polycarbonate | 0.40 |
2.3 |
High-insulation roofs and base panels |
Step-by-Step Calculation for Mixed Surfaces
- Divide the envelope into surface groups: Separate roof planes, sidewalls, end-walls, and base panels whenever they use different materials or thicknesses.
- Measure true exposed areas:
- Roof: Measure along the sloped rafter length (
sqrt(run^2 + rise^2)), not the flat floor footprint. - Sidewalls: Multiply length by height; split into upper glazing and lower base panel if materials differ.
- End-walls: Add the rectangular wall area (
width * eave_height) and any gable triangles (0.5 * width * ridge_rise). - Base panels / knee walls: Multiply exposed perimeter by panel height, omitting any insulated lean-to shared wall.
- Roof: Measure along the sloped rafter length (
- Assign U-values and compute
UA: Convert dimensions tom²(ft² * 0.092903) and multiply each surface area by its SI U-value (W/(m²·K)) to getUA_iinW/K. Sum allUA_ivalues for the total envelope conductanceUA_total. - Apply the clamped temperature difference: Calculate
delta_T = max(0, T_target - T_outdoor)inK(°F_diff * 5/9). - Convert to output units: Multiply
UA_total * delta_Tto obtainQ_condinW, then multiply by3.41214forBTU/h.
Illustrative Mixed-Surface Example
Illustrative assumptions: A freestanding gable greenhouse measuring 12.0 ft x 16.0 ft (3.66 m x 4.88 m, 192 ft² / 17.84 m² footprint), 6.0 ft (1.83 m) eaves, 3.0 ft (0.91 m) gable rise (6.71 ft / 2.04 m sloped rafter length), 2.0 ft (0.61 m) perimeter base panel in 16 mm triple-wall polycarbonate, 4.0 ft (1.22 m) upper sidewalls and end-walls in 8 mm twin-wall polycarbonate, and a 6 mm twin-wall polycarbonate roof. Target indoor temperature is 50°F (10.0°C) against a 20°F (-6.7°C) outdoor low (delta_T = 30°F / 16.67 K).
| Surface Group | Glazing Material | Area (ft² / m²) |
U-Value (BTU/(h·ft²·°F) / W/(m²·K)) |
Conductance UA (W/K) |
Heat Loss (BTU/h / W) |
|---|---|---|---|---|---|
| Roof (two slopes) | 6 mm twin-wall PC | 214.7 (19.94) |
0.62 (3.5) |
69.80 |
3,969 (1,163) |
| Upper sidewalls (2 sides) | 8 mm twin-wall PC | 128.0 (11.89) |
0.58 (3.3) |
39.24 |
2,232 (654) |
| Upper end-walls (2 ends + gables) | 8 mm twin-wall PC | 132.0 (12.26) |
0.58 (3.3) |
40.47 |
2,301 (674) |
| Base panel (full perimeter) | 16 mm triple-wall PC | 112.0 (10.41) |
0.40 (2.3) |
23.93 |
1,361 (399) |
| Total Envelope | Mixed | 586.7 (54.50) |
— | 173.44 |
9,864 (2,891) |
Note: Individual surface rows sum to 9,863 BTU/h (2,890 W) due to integer rounding; the exact SI total (173.44 W/K * 16.67 K) is 2,891 W (9,864 BTU/h). Because 2,891 W of conductive loss alone already exceeds a 1,440 W continuous 120V/15A circuit budget before adding air-infiltration heat loss, this configuration requires either higher-R glazing, a lower delta_T target, or higher-capacity heating.
Verification Checks
- Surface-to-footprint ratio: A gable greenhouse's exposed surface area is typically 2.5x to 3.5x its floor footprint (
586.7 ft²vs.192 ft²in the example above). If your summed surface area is close to the floor area, roof pitch and end-wall gables were omitted. - Unit consistency: Verify that
W/(m²·K)inputs are not mixed withft²areas. Using1 W/(m²·K) = 0.1761 BTU/(h·ft²·°F)keeps manual checks aligned with/greenhouse-climate/#calculator. - Warm-weather check: Test your formula or calculator entry with
T_outdoorset equal to or aboveT_target; the output must read0 BTU/h (0 W).
Real Failure Modes
- Using floor footprint for roof area: Substituting horizontal footprint area for sloped roof area underestimates roof conduction on steep-pitched hobby frames.
- Applying a single U-value to mixed envelopes: Assigning a wall or triple-wall base-panel U-value to the entire structure hides the disproportionate heat loss through thinner roof glazing.
- Unsealed multi-wall edges and open vents: Steady-state conduction assumes a closed envelope. Uncapped polycarbonate flutes, warped door sweeps, or cracked vents replace predictable conduction with uncontrolled convective air exchange.
- Double-counting wind or infiltration: Adding arbitrary wind percentages to
Q_condand then adding full ACH infiltration in Heating Loads inflates heater sizing beyond actual steady-state demand.
Guides in this section (3)
- Hoop-Tunnel Envelope Conduction Heat Loss CalculationCalculate hoop-tunnel conduction loss using the continuous arch arc surface area, semi-elliptical end-wall areas, and single-layer (6.8 W/(m2*K)) or double-layer inflated (4.0 W/(m2*K)) polyethylene U-values without applying separate wind multipliers.
- Polycarbonate Gable Conduction Heat Loss CalculationDecompose a polycarbonate gable greenhouse into rectangular sidewalls, sloped roof planes, triangular gable ends, and any insulated knee walls using thickness-specific multiwall U-values (2.3 to 3.9 W/(m2*K)) before summing steady-state conduction loss.
- Single-Glass Greenhouse Conduction Heat Loss CalculationAssign the 6.4 W/(m2*K) (1.13 BTU/(hr*ft2*F)) single-pane glass U-value across all glazed roof, sidewall, and gable panels while separating opaque masonry or timber knee-wall areas to prevent severe capacity undersizing.