Hoop-Tunnel Envelope Conduction Heat Loss Calculation
Calculate steady-state hoop-tunnel conduction heat loss from the exposed above-grade curved arch surface area, the two semi-elliptical end-wall areas, and the steady-state film U-value—1.20 BTU/(h·ft²·°F) (6.8 W/(m²·K)) for single-layer polyethylene or 0.70 BTU/(h·ft²·°F) (4.0 W/(m²·K)) for double-layer inflated polyethylene—without applying separate wind multipliers:
Greenhouse heating load & circuit budget calculator
Size winter greenhouse heat loss from exposed glazing U-values (excluding insulated lean-to walls) plus ACH air infiltration, and verify total branch-circuit load.
Q_cond = (U_arch * A_arch + U_end * 2 * A_end) * delta_T
For hoop tunnels up to 485 ft² (45 m²) of floor area, this conduction term belongs to the overall Envelope Conduction Heat Loss framework. Keep calculations aligned to SI units internally (W/(m²·K), m², K) and convert final heating capacity using 1 W = 3.412 BTU/h.
Boundary Conditions That Change the Answer
- Arch arc length vs. floor width: Heat conducts through the curved overhead film (
S_arc * L), not the ground footprint (W * L). Using footprint area underestimates roof/sidewall conduction by roughly35%–45%. - Double-layer inflation state: The
0.70 BTU/(h·ft²·°F)(4.0 W/(m²·K)) rating applies only while a continuous inflation blower maintains an air gap between the inner and outer films. If the blower fails or a tear lets the layers touch, conduction reverts to single-layer1.20 BTU/(h·ft²·°F)(6.8 W/(m²·K)), raising conductive heat loss by70%. - No wind multipliers on U-value: Published U-values already include standard exterior convective film resistance. Account for wind-driven air leakage separately in the air-infiltration sensible heat term (
0.018 BTU/(h·ft³·°F)or0.335 W/(m³·K) * volume * ACH * delta_T) rather than multiplyingQ_condby a wind factor. - Ground-contact skirt boundary: Exclude the interior soil or gravel floor from
A_totalin air-to-air conduction, but measureS_arcall the way down to the ground-contact skirt or baseboard where exterior air contacts the wall. - Mixed end-wall glazing: If end walls use rigid twin-wall polycarbonate instead of polyethylene film, calculate
2 * A_endusing the polycarbonate U-value and sumU * Aterms before multiplying bydelta_T.
Polyethylene and End-Wall Glazing U-Values
| Envelope Assembly | Imperial U-Value | Metric U-Value (SI) | Required Condition |
|---|---|---|---|
| Single-layer polyethylene film | 1.20 BTU/(h·ft²·°F) |
6.8 W/(m²·K) |
Tightly tensioned single film |
| Double-layer inflated polyethylene | 0.70 BTU/(h·ft²·°F) |
4.0 W/(m²·K) |
Active blower maintaining separated air gap |
4 mm (0.16 in) twin-wall polycarbonate (end wall) |
0.69 BTU/(h·ft²·°F) |
3.9 W/(m²·K) |
Sealed flutes at top and bottom |
6 mm (0.24 in) twin-wall polycarbonate (end wall) |
0.62 BTU/(h·ft²·°F) |
3.5 W/(m²·K) |
Sealed flutes at top and bottom |
8 mm (0.31 in) twin-wall polycarbonate (end wall) |
0.58 BTU/(h·ft²·°F) |
3.3 W/(m²·K) |
Sealed flutes at top and bottom |
10 mm (0.39 in) twin-wall polycarbonate (end wall) |
0.53 BTU/(h·ft²·°F) |
3.0 W/(m²·K) |
Sealed flutes at top and bottom |
Verify the exact glazing thickness and manufacturer U-value on product datasheets if your end walls use multi-wall panels or thermal-barrier films.
Measuring Arch Arc Length, End-Wall Area, and Skirt Boundaries
1. Continuous Arch Arc Length (S_arc) and Roof/Wall Area (A_arch)
For an existing hoop tunnel, pull a flexible tape measure directly over the exterior of a central hoop from the ground-contact skirt on one side, over the ridge, to the ground-contact skirt on the opposite side. Direct measurement captures custom bends, swaged joints, and Gothic peak profiles without geometric error.
When estimating before assembly, use the profile equations below (W = span width, H = ridge height, L = tunnel length):
- Semicircular hoop (
H = W / 2):S_arc = pi * (W / 2) A_arch = S_arc * L - Semi-elliptical hoop (
H != W / 2, no vertical knee walls): Leta = W / 2andb = H. Using Ramanujan's half-ellipse perimeter:S_arc = (pi / 2) * (3 * (a + b) - sqrt((3 * a + b) * (a + 3 * b))) A_arch = S_arc * L - Hoop with vertical knee walls (
h_wallon each side): Measure or calculate the curved upper archS_upperabove the knee-wall hip, then add both vertical walls:S_arc = 2 * h_wall + S_upper A_arch = S_arc * L
2. End-Wall Area (A_end)
For both front and rear end walls combined (2 * A_end):
- Semicircular end wall:
A_end = (pi / 8) * W^2 2 * A_end = (pi / 4) * W^2 - Semi-elliptical end wall:
A_end = (pi / 4) * W * H 2 * A_end = (pi / 2) * W * H - Knee-wall + semi-elliptical arch end wall:
A_end = (W * h_wall) + (pi / 4) * W * (H - h_wall)
Do not subtract door framing from A_end unless the door is an insulated opaque panel with a known lower U-value; standard poly-skinned or polycarbonate-skinned doors conduct heat at roughly the same rate as the surrounding end wall.
3. Ground-Contact Skirt Boundaries
| Skirt Construction | How to Treat in Q_cond |
Notes |
|---|---|---|
| Buried polyethylene trench skirt | Measure S_arc to soil grade |
Exclude buried underground film; include all film exposed to outdoor air |
Single-layer wiggle-wire baseboard (<= 1 ft / 300 mm wood) |
Keep full S_arc at film U-value |
Uninsulated dimensional lumber (~1.5 in / 38 mm) does not materially lower total tunnel loss |
Insulated perimeter knee wall (R-5+ foam-backed) |
Split knee-wall area out of A_arch |
Assign the insulated wall U-value (U = 1 / R_SI) to 2 * h_wall * L and film U-value to S_upper * L |
Step-by-Step Calculation (Illustrative Example)
Illustrative assumptions: A backyard semi-elliptical hoop tunnel measuring 14 ft wide (4.267 m), 24 ft long (7.315 m), with a 336 ft² (31.2 m²) footprint and an 8.5 ft (2.591 m) ridge height. Design temperatures are 50°F (10.0°C) inside and 20°F (-6.7°C) outside, giving delta_T = 30°F (16.67 K). Both the arch and end walls are covered in polyethylene film.
Step 1: Compute the Arch Arc Length and Arch Surface Area
In SI (a = 4.267 m / 2 = 2.134 m, b = 2.591 m):
S_arc = (3.1416 / 2) * (3 * (2.134 + 2.591) - sqrt((3 * 2.134 + 2.591) * (2.134 + 3 * 2.591)))
S_arc = 1.5708 * (14.175 - sqrt(8.993 * 9.907))
S_arc = 1.5708 * (14.175 - 9.439) = 7.439 m (24.41 ft)
A_arch = 7.439 m * 7.315 m = 54.42 m² (585.8 ft²)
Step 2: Compute Both End-Wall Areas
A_end = (3.1416 / 4) * 4.267 m * 2.591 m = 8.683 m² (93.5 ft²) per end wall
2 * A_end = 17.37 m² (186.9 ft²)
Step 3: Sum Total Exposed Envelope Area
Because the arch and end walls use the same polyethylene film:
A_total = 54.42 m² + 17.37 m² = 71.79 m² (772.7 ft²)
(If the end walls were 8 mm twin-wall polycarbonate instead, keep A_arch = 54.42 m² at 4.0 or 6.8 W/(m²·K) and 2 * A_end = 17.37 m² at 3.3 W/(m²·K).)
Step 4: Calculate Steady-State Conduction Heat Loss
- Single-layer polyethylene (
6.8 W/(m²·K)/1.20 BTU/(h·ft²·°F)):Q_cond = 6.8 W/(m²·K) * 71.79 m² * 16.67 K = 8,138 W (27,768 BTU/h) - Double-layer inflated polyethylene (
4.0 W/(m²·K)/0.70 BTU/(h·ft²·°F)):Q_cond = 4.0 W/(m²·K) * 71.79 m² * 16.67 K = 4,787 W (16,334 BTU/h)
At a 30°F (16.67 K) temperature lift, inflating a second layer reduces steady-state conductive heat loss by 11,434 BTU/h (3,351 W).
Verification Checks
- Tape vs. formula check: Compare your calculated
S_arcagainst a physical tape measurement over the center hoop. If they differ by more than3%, use the physical tape measurement. - Inflation air-gap check: On double-layer tunnels, confirm
1–4 in(25–100 mm) of air separation at mid-span between hoops and verify that the blower intake pulls dry indoor or filtered outdoor air so condensation does not pool and collapse the gap. - Skirt and end-wall seal check: Inspect the wiggle-wire channels, door sweeps, and ridge/hip transitions. Gaps that whistle or show daylight belong in air-infiltration load sizing, not conduction.
Real Failure Modes
- Floor-area substitution: Sizing conduction from
W * L(336 ft²/31.2 m²in the example) instead ofA_total(772.7 ft²/71.8 m²) cuts the calculated load by more than half and leaves the heater unable to hold temperature during clear, calm frost nights. - Unpowered or collapsed double poly: Relying on
0.70 BTU/(h·ft²·°F)(4.0 W/(m²·K)) when the inflation blower is off, unplugged, or feeding a punctured outer sheet causes conductive loss to jump70%overnight. - Double-counting wind: Multiplying
Q_condby a wind factor on top of adding ACH infiltration heat loss inflates the required heater size and can push electric heating loads past a120V/15Acontinuous circuit budget (1,440 W). - Ignoring wet-film contact at the skirt: When slack inner film rests directly against the outer film near the baseboard, that lower band conducts at the single-layer rate (
1.20 BTU/(h·ft²·°F)/6.8 W/(m²·K)) and promotes condensation drip along the perimeter.