Air Infiltration ACH Heat Loss Sizing

Open calculator ↓

Compute sensible infiltration heat loss directly from enclosed greenhouse air volume, an envelope-matched hourly air changes per hour (ACH) tier, and the indoor-to-outdoor design temperature difference using 0.018 BTU/(h·ft³·°F) (0.335 W/(m³·K)), without adding a separate wind multiplier. Combine that sensible infiltration load with exposed-surface envelope conduction to size total heating capacity for hobby food-growing greenhouses up to 485 ft² (45 m²).

Greenhouse heating load & circuit budget calculator

Size winter greenhouse heat loss from exposed glazing U-values (excluding insulated lean-to walls) plus ACH air infiltration, and verify total branch-circuit load.

Greenhouse geometry & exposed glazing

Lean-to excludes the shared insulated back wall. Hoop uses semi-elliptical/semicircular arch geometry (set eave height = 0 for ground-sprung tunnels). Glazing: 4–10 mm 2W PC = twin-wall, 16 mm 3W PC = triple-wall, double air poly = air-inflated double film; U shown as W/m²K / BTU/(h·ft²·°F). Hobby scope ≤ 45 m² (~485 ft²).

Design temperatures & air infiltration (ACH)

Air infiltration (ACH) captures air leakage and wind exposure directly—do not stack an extra wind multiplier on top.

Known branch-circuit continuous load check

Include all continuous devices sharing the same breaker. Default assumes a known 120V/15A continuous 80% budget (1,440 W) in EN or a conservative dedicated 230V/16A budget assumption (2,800 W) in DE/FR.

Boundary conditions that shift the result:

  • Envelope tightness and wind exposure: Switching from a gasketed, caulked polycarbonate structure (0.5–0.75 ACH) to a wind-exposed or loosely lapped glazing shell (1.5–2.5 ACH) triples infiltration heat loss at the same interior volume.
  • Double-counting wind: The ACH tier already accounts for wind-driven air exchange across gaps; applying an extra wind factor to either infiltration or conduction inflates heater sizing.
  • Enclosed volume vs. footprint: Tall gable or hoop profiles increase air volume per square foot of floor area, raising infiltration loss even when footprint stays small.
  • Shared insulated walls: In a lean-to greenhouse attached to a conditioned building, exclude the insulated shared wall from exposed conduction area and treat it as a sealed boundary unless unsealed pass-throughs exist.

Sensible Infiltration Equation and Unit Alignment

Sensible infiltration heat loss measures the energy required to warm cold outdoor air leaking into the greenhouse up to the target indoor air temperature. Keep internal calculations aligned to the SI equation and convert outputs to North American units:

  • SI internal equation: Q_inf (W) = 0.335 W/(m³·K) x Volume (m³) x ACH (1/h) x delta-T (K or °C)
  • North American equivalent: Q_inf (BTU/h) = 0.018 BTU/(h·ft³·°F) x Volume (ft³) x ACH (1/h) x delta-T (°F)

Where:

  • Volume is the actual enclosed interior air volume of the conditioned greenhouse, not the exterior ground footprint multiplied by eaves height.
  • ACH is the hourly air-change rate selected from the physical envelope condition below.
  • delta-T is T_inside_target - T_outside_design (the coldest expected nighttime temperature for the growing season).

This sensible equation assumes dry-air heat capacity near standard atmospheric pressure and does not add latent moisture-removal load, because cold winter outdoor air entering a heated hobby greenhouse holds minimal absolute moisture before warming.


Selecting an Hourly ACH Tier

Select one ACH tier based on physical construction, perimeter sealing, and site wind exposure. Do not stack an extra wind-speed multiplier onto the result.

Envelope Tier Typical ACH (1/h) Physical Envelope Indicators Site Wind Exposure
Tight 0.50 – 0.75 Continuous perimeter sill gaskets, caulked polycarbonate H-channels/U-profiles, weatherstripped door frames with floor sweeps, sealed exhaust louvers with backdraft dampers Sheltered yard, fence/hedge windbreak, or lean-to with one shared building wall
Standard 0.75 – 1.25 Typical hobby kit assembly with standard glazing clips, uncaulked panel joints, single-layer door weatherstripping, or manually latched ridge vents without tight rubber seals Moderate exposure with partial windbreak on at least one side
Wind-Exposed / Leaky 1.50 – 2.50 Lapped single glass panes without glazing putty, unsealed base sills on gravel/soil, warped vent sashes, unsealed exhaust-fan shutters, or worn single-poly film seams Open ridge, hilltop, or unprotected yard exposed to sustained winter winds

When to choose the upper end of a tier: Pick the higher ACH value in a tier if the greenhouse uses gravity-operated louvers without motorized sealing dampers, has sliding doors instead of hinged gasketed doors, or relies on frequent manual entry during cold nights.


Combining Infiltration Loss with Envelope Conduction

Total design heating load is the sum of conductive heat transfer through exposed glazing/wall surfaces and sensible air infiltration through envelope gaps. For full surface-area measurement rules and glazing selection, see the parent Heating Loads reference.

Q_total = Q_cond + Q_inf

Where:

  • Q_cond (W) = Sum(U_i x A_i) x delta-T (°C)
  • Q_cond (BTU/h) = Sum(U_i x A_i) x delta-T (°F)

Exposed Envelope U-Values for Conduction

Use the exposed surface U-value for each distinct glazing or uninsulated wall section, excluding any insulated lean-to shared wall:

Glazing / Envelope Material U-Value: BTU/(h·ft²·°F) U-Value: W/(m²·K)
Single polyethylene film 1.20 6.8
Single glass 1.13 6.4
Double polyethylene film (air-inflated) 0.70 4.0
4 mm twin-wall polycarbonate 0.69 3.9
6 mm twin-wall polycarbonate 0.62 3.5
8 mm twin-wall polycarbonate 0.58 3.3
10 mm twin-wall polycarbonate 0.53 3.0
16 mm triple-wall polycarbonate 0.40 2.3

Step-by-Step Sizing Procedure

  1. Measure enclosed air volume (V): Calculate interior volume from actual frame geometry.
    • Gable greenhouse: V = Length x Width x (Eave_Height + 0.5 x (Peak_Height - Eave_Height))
    • Hoop / Quonset greenhouse: Use the cross-sectional area of the arch multiplied by length, verified against manufacturer interior volume or physical ridge/width measurements.
  2. Determine design delta-T: Subtract your lowest expected outdoor night temperature from your minimum crop-safe indoor temperature (for example, 50 °F [10 °C] inside minus 14 °F [-10 °C] outside gives delta-T = 36 °F [20 °C]).
  3. Assign the ACH tier: Inspect sill plates, door sweeps, vent gaskets, and louver dampers against the ACH table above. Choose one value (do not add a separate wind multiplier).
  4. Compute Q_inf:
    • SI: Q_inf = 0.335 x V_m3 x ACH x delta-T_C
    • US: Q_inf = 0.018 x V_ft3 x ACH x delta-T_F
  5. Compute Q_cond and sum Q_total: Multiply each exposed surface area by its U-value and delta-T, sum all exposed surfaces (excluding insulated lean-to shared walls), and add Q_inf to get Q_total.
  6. Check electric circuit budget (if electric heating is used): Add the heater's continuous input wattage to all existing continuous loads on the same circuit (circulation fans, nutrient pumps, environmental controllers). On a standard 120V/15A continuous circuit budget, total continuous load must stay <= 1,440 W (<= 4,913 BTU/h equivalent electric resistance heat). Verify actual nameplate amperage and wattage on equipment datasheets before deployment.

Illustrative Worked Example (240 ft² / 22.3 m² Hobby Greenhouse)

Illustrative assumptions:

  • Freestanding gable greenhouse: 20 ft x 12 ft (6.10 m x 3.66 m), 240 ft² (22.3 m²) footprint, 8.0 ft (2.44 m) average interior height.
  • Enclosed volume: V = 1,920 ft³ (54.4 m³).
  • Exposed glazing: 750 ft² (69.7 m²) of 8 mm twin-wall polycarbonate (U = 0.58 BTU/(h·ft²·°F) / 3.3 W/(m²·K)), standard kit sealing (ACH = 1.0).
  • Design temperature difference: delta-T = 36 °F (20 °C).

1. Sensible infiltration loss (Q_inf):

  • SI: 0.335 W/(m³·K) x 54.4 m³ x 1.0 x 20 K = 364 W
  • US: 0.018 BTU/(h·ft³·°F) x 1,920 ft³ x 1.0 x 36 °F = 1,244 BTU/h

2. Envelope conduction loss (Q_cond):

  • SI: 3.3 W/(m²·K) x 69.7 m² x 20 K = 4,600 W
  • US: 0.58 BTU/(h·ft²·°F) x 750 ft² x 36 °F = 15,660 BTU/h

3. Combined design heating load (Q_total):

  • Q_total = 15,660 + 1,244 = 16,904 BTU/h (4,964 W)
  • At 1.0 ACH, infiltration represents 7.4% of total heating demand. If the same structure were unsealed and wind-exposed (2.5 ACH), Q_inf would rise to 3,110 BTU/h (911 W), pushing total load to 18,770 BTU/h (5,511 W).
  • Circuit check: Because 4,964 W exceeds the 1,440 W continuous limit of a single 120V/15A circuit, this design requires either a higher-capacity heating source or a smaller/higher-R thermal zone (such as an internal frost tent) if limited to one 120V/15A outlet.

Verification Checks

  • Physical volume check: Confirm actual ridge and eave heights with a tape measure rather than relying on nominal catalog dimensions, which sometimes quote exterior base-to-finial height.
  • Draft and damper check: Run a smoke-pencil or incense test along sill plates, door sweeps, ridge-vent corners, and closed exhaust shutters on a breezy day. Visible smoke pull indicates the envelope belongs in the Standard or Wind-Exposed tier rather than Tight.
  • Nameplate wattage check: Read the steady-state continuous wattage (W) and amperage (A) on the heater and fan datasheets rather than using nominal BTU marketing claims.

Real Failure Modes

  • Double-counting wind exposure: Adding a 15–30% "wind factor" on top of a 1.5–2.5 ACH wind-exposed tier oversizes the heater, causing rapid short-cycling and temperature swings near the thermostat sensor.
  • Assuming kit polycarbonate equals a tight envelope: Uncaulked twin-wall polycarbonate joints and unsealed base channels often leak at 1.0–1.5 ACH even when the glazing itself has a low U-value.
  • Confusing exhaust fan CFM with winter ACH: Daytime exhaust ventilation rates (often 45–60 ACH equivalent) are active mechanical airflow, not passive closed-envelope winter infiltration.
  • Overloading a 120V/15A circuit: Pairing a 1,500 W space heater with a 60 W circulation fan and a 50 W hydroponic pump on one 120V/15A circuit exceeds the 1,440 W continuous load ceiling and trips the breaker during overnight frost events.
  • Leaving unsealed exhaust louvers open in winter: A single 12 in x 12 in (305 mm x 305 mm) stuck or uninsulated exhaust louver can turn a 0.75 ACH greenhouse into a 2.0+ ACH heat sink on windy nights.