Hoop-Tunnel Air Infiltration & ACH Heat Loss Sizing

Open calculator ↓

Compute hoop-tunnel internal volume from the arch cross-section and select a 1.25 to 2.0 ACH tier for roll-up curtain seams and end-wall doors—or 0.75 to 1.25 ACH for continuous lock-channel seals—at 0.018 BTU/(hr·ft³·°F) (0.335 W/(m³·K)) without adding an extra wind multiplier. Combine this sensible infiltration load directly with arch and end-wall conduction loss to size total heating capacity.

Cross-section of an arched hoop tunnel greenhouse anchored with ground stakes and lower side roll-up ventilation curtainHOOP TUNNEL & GROUND ANCHORS Arch span He = 0 / sidewall Ground stakes Roll-up venting Curved roof sheds snow; verify film tension & anchors

Greenhouse heating load & circuit budget calculator

Size winter greenhouse heat loss from exposed glazing U-values (excluding insulated lean-to walls) plus ACH air infiltration, and verify total branch-circuit load.

Greenhouse geometry & exposed glazing

Lean-to excludes the shared insulated back wall. Hoop uses semi-elliptical/semicircular arch geometry (set eave height = 0 for ground-sprung tunnels). Glazing: 4–10 mm 2W PC = twin-wall, 16 mm 3W PC = triple-wall, double air poly = air-inflated double film; U shown as W/m²K / BTU/(h·ft²·°F). Hobby scope ≤ 45 m² (~485 ft²).

Design temperatures & air infiltration (ACH)

Air infiltration (ACH) captures air leakage and wind exposure directly—do not stack an extra wind multiplier on top.

Known branch-circuit continuous load check

Include all continuous devices sharing the same breaker. Default assumes a known 120V/15A continuous 80% budget (1,440 W) in EN or a conservative dedicated 230V/16A budget assumption (2,800 W) in DE/FR.

Boundary conditions that shift the sizing:

  • Roll-up sidewalls vs. fixed lock-channel film: Unsealed curtain overlap edges and hand-crank pockets raise leakage into the 1.25–2.0 ACH tier even when curtains are rolled down; continuous aluminum lock-channel extrusions with spring wire drop leakage to 0.75–1.25 ACH.
  • End-wall door framing: Unweatherstripped hinged or sliding doors add perimeter crack area; use the upper end of the selected ACH tier (1.25 or 2.0 ACH) when end-wall doors lack bulb gaskets or threshold sweeps.
  • No double-counting wind: The ACH tier already embeds typical wind-driven and stack-driven air exchange across tunnel seams. Do not multiply the result by an external wind factor.
  • Arch vs. rectangular volume: Treating a hoop tunnel as a rectangular box (W × H_ridge × L) overstates enclosed air volume by roughly 20–27% on a semicircular Quonset, inflating calculated infiltration load.

Hoop-Tunnel Volume & Surface Geometry

Hoop tunnels enclosed with polyethylene film or twin-wall polycarbonate have curved upper cross-sections that must be integrated rather than boxed. Compute cross-sectional area (A_cs) first, then multiply by tunnel length (L) for enclosed volume (V).

Tunnel Profile Cross-Sectional Area (A_cs) Enclosed Volume (V) Curved + Sidewall Perimeter (P_arch)
Quonset (pure semicircle, no knee wall) (3.1416 × W²) / 8 A_cs × L (3.1416 × W) / 2
Semicircular arch on vertical knee walls (W × H_wall) + ((3.1416 × W²) / 8) A_cs × L (2 × H_wall) + ((3.1416 × W) / 2)
Gothic / pointed arch (non-circular) Measure width at base, knee, and mid-arch; sum trapezoidal slices A_cs × L Measure arc length directly over one bow with a flexible tape

Note: Total exposed skin area for conduction equals (P_arch × L) + (2 × A_cs) when both end-walls are above grade and glazed.


ACH Tier Selection by Seam & Seal Construction

Select the hourly air-change rate (ACH) based on physical seam hardware rather than generic greenhouse defaults in the parent infiltration and ACH heat loss reference.

Envelope & Seam Configuration Design ACH Tier Low-End Trigger High-End Trigger
Continuous lock-channel seals (film locked into extrusion at base, ridge, and end-wall bows; weatherstripped door) 0.75 – 1.25 ACH Double-layer inflated poly; gasketed door with threshold sweep; sheltered yard Single-layer poly; un-gasketed door frame; exposed windward site
Roll-up curtain seams & end-wall doors (manual roll-up sides tucked behind retention straps; standard hinged/sliding doors) 1.25 – 2.0 ACH Curtains drop into a bottom retention pocket with tight end-wall baffles Loose curtain overlap without pocket; warped door jambs; open ridge vents or unsealed fan shutters

Governing Heat-Loss Equations

Align all calculations to the shared SI internal equations and convert to North American units as needed:

1. Sensible air-infiltration heat loss (Q_inf):

  • SI: Q_inf (W) = 0.335 × V (m³) × ACH × delta_T (K)
  • North American: Q_inf (BTU/h) = 0.018 × V (ft³) × ACH × delta_T (°F)

2. Arch and end-wall conduction loss (Q_cond):

  • SI: Q_cond (W) = sum(U_i × A_i) × delta_T (K)
  • North American: Q_cond (BTU/h) = sum(U_i × A_i) × delta_T (°F)

Reference glazing U-values (exposed surfaces):

  • Single poly: 1.20 BTU/(hr·ft²·°F) (6.8 W/(m²·K))
  • Double poly (inflated): 0.70 BTU/(hr·ft²·°F) (4.0 W/(m²·K))
  • 4 mm twin-wall polycarbonate: 0.69 BTU/(hr·ft²·°F) (3.9 W/(m²·K))
  • 6 mm twin-wall polycarbonate: 0.62 BTU/(hr·ft²·°F) (3.5 W/(m²·K))
  • 8 mm twin-wall polycarbonate: 0.58 BTU/(hr·ft²·°F) (3.3 W/(m²·K))
  • 10 mm twin-wall polycarbonate: 0.53 BTU/(hr·ft²·°F) (3.0 W/(m²·K))

3. Combined design heating load (Q_total):

  • Q_total = Q_cond + Q_inf

Step-by-Step Sizing Procedure (With Worked Example)

Illustrative backyard tunnel assumptions (verify against your actual frame):

  • Width W = 12 ft (3.66 m), Length L = 24 ft (7.32 m) -> footprint 288 ft² (26.8 m²).
  • Vertical knee walls H_wall = 4 ft (1.22 m) topped by a 6 ft (1.83 m) radius semicircular arch (ridge height 10 ft / 3.05 m).
  • Glazing: inflated double poly (U = 0.70 BTU/(hr·ft²·°F) / 4.0 W/(m²·K)).
  • Design temperature difference: interior target 50°F (10.0°C) at exterior low 20°F (-6.7°C) -> delta_T = 30°F (16.7 K).

Step 1: Compute cross-sectional area and internal volume

  • A_cs = (12 × 4) + ((3.1416 × 12²) / 8) = 48 + 56.55 = 104.55 ft² (9.71 m²)
  • V = 104.55 × 24 = 2,509 ft³ (71.1 m³)

Step 2: Select the ACH tier and compute infiltration loss

  • Option A — Roll-up curtain sidewalls + standard door (1.5 ACH midpoint):
    • Q_inf = 0.018 × 2,509 × 1.5 × 30 = 2,032 BTU/h (0.335 × 71.1 × 1.5 × 16.7 = 596 W)
  • Option B — Continuous lock-channel seals + gasketed door (1.0 ACH midpoint):
    • Q_inf = 0.018 × 2,509 × 1.0 × 30 = 1,355 BTU/h (0.335 × 71.1 × 1.0 × 16.7 = 397 W)

Step 3: Compute arch and end-wall conduction loss

  • P_arch = (2 × 4) + ((3.1416 × 12) / 2) = 8 + 18.85 = 26.85 ft (8.18 m)
  • A_total = (26.85 × 24) + (2 × 104.55) = 644.4 + 209.1 = 853.5 ft² (79.3 m²)
  • Q_cond = 0.70 × 853.5 × 30 = 17,924 BTU/h (4.0 × 79.3 × 16.7 = 5,297 W)

Step 4: Sum total load and check electrical circuit limits

  • With roll-up curtains (1.5 ACH): Q_total = 17,924 + 2,032 = 19,956 BTU/h (5,893 W in SI)
  • With lock-channel seals (1.0 ACH): Q_total = 17,924 + 1,355 = 19,279 BTU/h (5,694 W in SI)
  • Circuit-budget check: A single 120V/15A continuous circuit budget caps total load (existing fans/pumps + heater input) at 1,440 W (~4,913 BTU/h). Because 5,694–5,893 W exceeds 1,440 W, a single 120V/15A electric heater cannot hold a 30°F (16.7 K) lift in a 12 × 24 ft tunnel; use 1,440 W only for narrower frost-protection differentials (under ~7.5°F / 4.2 K lift) or size a dedicated heating source rated for the full load.

Field Verification Checks

  1. Measure true bow geometry: Measure knee-wall height (H_wall), interior span (W), and ridge height (H_ridge) at two intermediate bows to confirm whether the frame is a true semicircle (H_ridge = H_wall + W/2) or a compressed/pointed arch.
  2. Inspect perimeter seams at dusk: Run a bright flashlight along the outside of roll-up curtain pockets, end-wall door frames, and exhaust shutter louvers while standing inside; visible light gaps indicate leakage above 1.5 ACH.
  3. Verify nameplate continuous wattage: Confirm all circulation fans, inflation blowers, and irrigation pumps running concurrently with electric heaters, and verify total continuous draw stays <= 1,440 W on any 120V/15A circuit.

Real Failure Modes

  • Unbaffled roll-up curtain ends: Leaving triangular gaps where the roll-up pipe meets the end-wall framing bypasses the curtain pocket and pushes actual air exchange well above 2.0 ACH during crosswinds, causing rapid temperature collapse on the windward side.
  • Exhaust shutter backdrafting: Gravity exhaust shutters without magnetic latches or motorized dampers flutter open under negative wind pressure, turning a 1.0 ACH lock-channel tunnel into a 2.0+ ACH chimney.
  • Double-counting wind multipliers: Applying an extra 1.2–1.5× wind factor on top of a 1.5–2.0 ACH roll-up tier oversizes heater output, causing short-cycling, sharp humidity swings, and tripped breakers when heaters share circuits with blowers.
  • Single-layer poly condensation + infiltration coupling: In single-poly tunnels (U = 1.20 BTU/(hr·ft²·°F) / 6.8 W/(m²·K)), cold-wall condensation drips along the baseboard; if baseboard trim is not sealed, cold exterior air infiltrates right across the wet crop zone at ground level.