Hoop-Tunnel Air Infiltration & ACH Heat Loss Sizing
Compute hoop-tunnel internal volume from the arch cross-section and select a 1.25 to 2.0 ACH tier for roll-up curtain seams and end-wall doors—or 0.75 to 1.25 ACH for continuous lock-channel seals—at 0.018 BTU/(hr·ft³·°F) (0.335 W/(m³·K)) without adding an extra wind multiplier. Combine this sensible infiltration load directly with arch and end-wall conduction loss to size total heating capacity.
Greenhouse heating load & circuit budget calculator
Size winter greenhouse heat loss from exposed glazing U-values (excluding insulated lean-to walls) plus ACH air infiltration, and verify total branch-circuit load.
Boundary conditions that shift the sizing:
- Roll-up sidewalls vs. fixed lock-channel film: Unsealed curtain overlap edges and hand-crank pockets raise leakage into the 1.25–2.0 ACH tier even when curtains are rolled down; continuous aluminum lock-channel extrusions with spring wire drop leakage to 0.75–1.25 ACH.
- End-wall door framing: Unweatherstripped hinged or sliding doors add perimeter crack area; use the upper end of the selected ACH tier (1.25 or 2.0 ACH) when end-wall doors lack bulb gaskets or threshold sweeps.
- No double-counting wind: The ACH tier already embeds typical wind-driven and stack-driven air exchange across tunnel seams. Do not multiply the result by an external wind factor.
- Arch vs. rectangular volume: Treating a hoop tunnel as a rectangular box (
W × H_ridge × L) overstates enclosed air volume by roughly 20–27% on a semicircular Quonset, inflating calculated infiltration load.
Hoop-Tunnel Volume & Surface Geometry
Hoop tunnels enclosed with polyethylene film or twin-wall polycarbonate have curved upper cross-sections that must be integrated rather than boxed. Compute cross-sectional area (A_cs) first, then multiply by tunnel length (L) for enclosed volume (V).
| Tunnel Profile | Cross-Sectional Area (A_cs) |
Enclosed Volume (V) |
Curved + Sidewall Perimeter (P_arch) |
|---|---|---|---|
| Quonset (pure semicircle, no knee wall) | (3.1416 × W²) / 8 |
A_cs × L |
(3.1416 × W) / 2 |
| Semicircular arch on vertical knee walls | (W × H_wall) + ((3.1416 × W²) / 8) |
A_cs × L |
(2 × H_wall) + ((3.1416 × W) / 2) |
| Gothic / pointed arch (non-circular) | Measure width at base, knee, and mid-arch; sum trapezoidal slices | A_cs × L |
Measure arc length directly over one bow with a flexible tape |
Note: Total exposed skin area for conduction equals (P_arch × L) + (2 × A_cs) when both end-walls are above grade and glazed.
ACH Tier Selection by Seam & Seal Construction
Select the hourly air-change rate (ACH) based on physical seam hardware rather than generic greenhouse defaults in the parent infiltration and ACH heat loss reference.
| Envelope & Seam Configuration | Design ACH Tier | Low-End Trigger | High-End Trigger |
|---|---|---|---|
| Continuous lock-channel seals (film locked into extrusion at base, ridge, and end-wall bows; weatherstripped door) | 0.75 – 1.25 ACH | Double-layer inflated poly; gasketed door with threshold sweep; sheltered yard | Single-layer poly; un-gasketed door frame; exposed windward site |
| Roll-up curtain seams & end-wall doors (manual roll-up sides tucked behind retention straps; standard hinged/sliding doors) | 1.25 – 2.0 ACH | Curtains drop into a bottom retention pocket with tight end-wall baffles | Loose curtain overlap without pocket; warped door jambs; open ridge vents or unsealed fan shutters |
Governing Heat-Loss Equations
Align all calculations to the shared SI internal equations and convert to North American units as needed:
1. Sensible air-infiltration heat loss (Q_inf):
- SI:
Q_inf (W) = 0.335 × V (m³) × ACH × delta_T (K) - North American:
Q_inf (BTU/h) = 0.018 × V (ft³) × ACH × delta_T (°F)
2. Arch and end-wall conduction loss (Q_cond):
- SI:
Q_cond (W) = sum(U_i × A_i) × delta_T (K) - North American:
Q_cond (BTU/h) = sum(U_i × A_i) × delta_T (°F)
Reference glazing U-values (exposed surfaces):
- Single poly:
1.20 BTU/(hr·ft²·°F)(6.8 W/(m²·K)) - Double poly (inflated):
0.70 BTU/(hr·ft²·°F)(4.0 W/(m²·K)) - 4 mm twin-wall polycarbonate:
0.69 BTU/(hr·ft²·°F)(3.9 W/(m²·K)) - 6 mm twin-wall polycarbonate:
0.62 BTU/(hr·ft²·°F)(3.5 W/(m²·K)) - 8 mm twin-wall polycarbonate:
0.58 BTU/(hr·ft²·°F)(3.3 W/(m²·K)) - 10 mm twin-wall polycarbonate:
0.53 BTU/(hr·ft²·°F)(3.0 W/(m²·K))
3. Combined design heating load (Q_total):
Q_total = Q_cond + Q_inf
Step-by-Step Sizing Procedure (With Worked Example)
Illustrative backyard tunnel assumptions (verify against your actual frame):
- Width
W = 12 ft (3.66 m), LengthL = 24 ft (7.32 m)-> footprint288 ft² (26.8 m²). - Vertical knee walls
H_wall = 4 ft (1.22 m)topped by a6 ft (1.83 m)radius semicircular arch (ridge height10 ft / 3.05 m). - Glazing: inflated double poly (
U = 0.70 BTU/(hr·ft²·°F)/4.0 W/(m²·K)). - Design temperature difference: interior target
50°F (10.0°C)at exterior low20°F (-6.7°C)->delta_T = 30°F (16.7 K).
Step 1: Compute cross-sectional area and internal volume
A_cs = (12 × 4) + ((3.1416 × 12²) / 8) = 48 + 56.55 = 104.55 ft² (9.71 m²)V = 104.55 × 24 = 2,509 ft³ (71.1 m³)
Step 2: Select the ACH tier and compute infiltration loss
- Option A — Roll-up curtain sidewalls + standard door (1.5 ACH midpoint):
Q_inf = 0.018 × 2,509 × 1.5 × 30 = 2,032 BTU/h(0.335 × 71.1 × 1.5 × 16.7 = 596 W)
- Option B — Continuous lock-channel seals + gasketed door (1.0 ACH midpoint):
Q_inf = 0.018 × 2,509 × 1.0 × 30 = 1,355 BTU/h(0.335 × 71.1 × 1.0 × 16.7 = 397 W)
Step 3: Compute arch and end-wall conduction loss
P_arch = (2 × 4) + ((3.1416 × 12) / 2) = 8 + 18.85 = 26.85 ft (8.18 m)A_total = (26.85 × 24) + (2 × 104.55) = 644.4 + 209.1 = 853.5 ft² (79.3 m²)Q_cond = 0.70 × 853.5 × 30 = 17,924 BTU/h(4.0 × 79.3 × 16.7 = 5,297 W)
Step 4: Sum total load and check electrical circuit limits
- With roll-up curtains (1.5 ACH):
Q_total = 17,924 + 2,032 = 19,956 BTU/h(5,893 Win SI) - With lock-channel seals (1.0 ACH):
Q_total = 17,924 + 1,355 = 19,279 BTU/h(5,694 Win SI) - Circuit-budget check: A single
120V/15Acontinuous circuit budget caps total load (existing fans/pumps + heater input) at1,440 W(~4,913 BTU/h). Because5,694–5,893 Wexceeds1,440 W, a single120V/15Aelectric heater cannot hold a30°F (16.7 K)lift in a12 × 24 fttunnel; use1,440 Wonly for narrower frost-protection differentials (under~7.5°F / 4.2 Klift) or size a dedicated heating source rated for the full load.
Field Verification Checks
- Measure true bow geometry: Measure knee-wall height (
H_wall), interior span (W), and ridge height (H_ridge) at two intermediate bows to confirm whether the frame is a true semicircle (H_ridge = H_wall + W/2) or a compressed/pointed arch. - Inspect perimeter seams at dusk: Run a bright flashlight along the outside of roll-up curtain pockets, end-wall door frames, and exhaust shutter louvers while standing inside; visible light gaps indicate leakage above
1.5 ACH. - Verify nameplate continuous wattage: Confirm all circulation fans, inflation blowers, and irrigation pumps running concurrently with electric heaters, and verify total continuous draw stays
<= 1,440 Won any120V/15Acircuit.
Real Failure Modes
- Unbaffled roll-up curtain ends: Leaving triangular gaps where the roll-up pipe meets the end-wall framing bypasses the curtain pocket and pushes actual air exchange well above
2.0 ACHduring crosswinds, causing rapid temperature collapse on the windward side. - Exhaust shutter backdrafting: Gravity exhaust shutters without magnetic latches or motorized dampers flutter open under negative wind pressure, turning a
1.0 ACHlock-channel tunnel into a2.0+ ACHchimney. - Double-counting wind multipliers: Applying an extra
1.2–1.5×wind factor on top of a1.5–2.0 ACHroll-up tier oversizes heater output, causing short-cycling, sharp humidity swings, and tripped breakers when heaters share circuits with blowers. - Single-layer poly condensation + infiltration coupling: In single-poly tunnels (
U = 1.20 BTU/(hr·ft²·°F)/6.8 W/(m²·K)), cold-wall condensation drips along the baseboard; if baseboard trim is not sealed, cold exterior air infiltrates right across the wet crop zone at ground level.